The minimum blowdown for a spring loaded safety valve shall be of what percent of set pressure? - Answer 10% How is the main steam pressure gages tested? - Answer With an inspectors gage Who is in charge of the code for any plumbing installations? - Answer The nyc plumbing code When will anchorage or guides be inspected? - Answer Annually How many brass washout plugs does a miniature boiler have? - Answer 3 brass washout plugs, 1" in size How often is HP piping expansion joints inspected? - Answer Weekly How long should a hydronic system be pressure tested for? - Answer 2 hours at no less than 100 psig How is a gage protected from excessive pressure? - Answer Shut off cock Who is authorized to witness a test on a gas piping system? - Answer Plumbing inspector, architect, licensed PE, master plumber, agency by the DOB How should a remote disconnect be labeled? - Answer Remote control for burner When is a fusible plug not needed to be installed on a boiler? - Answer Over 200 psig When shall a power boiler with a MAWP over 400 be tested? - Answer Pressure tested annually