S12 Certificate of Fitness
Sprinkler Exam Questions
and Complete Solutions
Graded A+
Denning [Date] [Course title]
,When the pump is in operation a small water leak on the pump bearings is desirable and should not be
considered a malfunction. Additionally, water should discharge from a ---- relief valve (electric pump) or
--- exchanger (diesel pump) while the fire pump is operating under a "no-flow" condition. - Answer:
circulation /heat
A sprinkler system is a - Answer: fire extinguishing system, other than a water mist system, that utilizes
water as the extinguishing agent.
Inspection, testing, servicing and other maintenance of sprinkler systems must be - Answer: personally
supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011
edition.
All multiple dwellings, factories, office buildings, warehouses, stores and offices, theaters and music
halls, hospitals and asylums, and all public schools and other public buildings, churches and other places
where large numbers of persons are congregated for purposes of worship, instruction, amusement, and
all piers, bulkheads, wharves, pier sheds, bulkhead sheds or other waterfront structures shall provide -
Answer: fire extinguishers, buckets, axes, fire hooks, fire doors and other means of preventing and
extinguishing fires as the commissioner may direct.
Required fire protection systems shall be extended or altered as necessary to maintain and continued
protection whenever - Answer: the building or structure is altered. Systems not complying with this
section shall be considered to be impaired.
It shall be unlawful to install or maintain any fire protection system or device that has - Answer: the
physical appearance of fire protection equipment but that does not perform a fire protection function
where it may be confused with actual fire protection equipment. An example would be a CCTV camera
that is installed inside a shell that resembles a sprinkler head
SPRINKLER AND/OR STANDPIPE SYSTEM MAINTENANCE AND INSPECTIONS - Answer:
1. Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required
by NFPA #25 2011 edition by a competent person holding a S-12 Certificate of Fitness and employed or
contracted by the owner, to see that all parts of the system are in good working order, and that the Fire
Department connection(s), if any, are ready for immediate use by the Fire Department. A detailed
,record shall be kept on the premises or other approved location, for a minimum of 3 years for
examination by any representative of the Fire Department. - Answer:
2.A supply of at least six extra sprinkler heads shall be kept available on the premises, to replace
promptly any fused or damaged sprinklers. Any head which has opened or has been damaged shall be
replaced immediately with sprinkler head of similar characteristics such as operating temperature,
orifice size, deflector orientation and thermal sensitivity. - Answer:
3. At least once every five years, the Fire Department connection or connections for a sprinkler system
shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire Department use.
The test shall be arranged to be conducted by a Master Fire Suppression Piping Contractor in the
presence of a Fire Department representative.
The contractor shall be hired by the owner or the owner's representative. - Answer:
4.There shall be one or more employees or individuals contracted by the owner with a Certificate of
Fitness to inspect the sprinkler system following the standard of the NFPA 25 of 2011. - Answer:
Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required
by NFPA #25 2011 edition by - Answer: competent person holding a S-12 Certificate of Fitness and
employed or contracted by the owner, to see that all parts of the system are in good working order, and
that the Fire Department connection(s), if any, are ready for immediate use by the Fire Department.
A detailed record shall be kept on the premises or other approved location, for a minimum of - Answer:
3 years for examination by any representative of the Fire Department.
A supply of at least----extra sprinkler heads shall be kept available on the premises, to replace promptly
any fused or damaged sprinklers. - Answer: 6
Any head which has ----or has been----1. shall be replaced immediately with sprinkler head of similar
characteristics such as operating temperature, orifice size, deflector orientation and thermal sensitivity.
- Answer: opened/damaged
At least once every ---- years - Answer: Fire Department connection or connections for a sprinkler
system shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire
Department use.
, At least once every five years, the Fire Department connection or connections for a sprinkler system
shall be subjected to a hydrostatic pressure test to demonstrate its suitability for Fire Department use.
The test shall be arranged to be conducted by a ----by a----The contractor shall be hired by----- - Answer:
Master Fire Suppression Piping Contractor/1. a Fire Department representative/the owner or the
owner's representative.
There shall be---more employees or individuals contracted by the owner with a----Certificate of Fitness
1. inspect the sprinkler system following the standard of the NFPA 25 of 2011. - Answer: one/COF
II. RESPONSIBILITY OF THE BUILDING OWNER - Answer:
It shall be the -----'s responsibility to maintain the sprinkler system and to determine the individual
qualifications and competencies of the COF holder that performs the functions related to inspection,
testing and maintenance of such system. - Answer: owner's
The building owner shall assign an ----to comply with the requirements of study material. - Answer:
impairment coordinator
The impairment coordinator shall take the action(s) when - Answer: a standpipe system, sprinkler
system or fire alarm system is out of service.
The impairment coordinator shall maintain records of all - Answer: system inspections, tests, servicing
and other items of maintenance
The impairment coordinator's records of system inspections, tests, servicing and other items of
maintenance shall be kept on the premises or other approved location for a minimum of --- and made
available for inspection by any member of---- - Answer: 3 years/FDNY
In absence of a specific designee,the ---shall be considered the impairment coordinator. - Answer:
building owner
III. OUT OF SERVICE SYSTEMS (OOS) - Answer: