NICET PREP FIRE ALARMS 2024-2025 EXAM |COMPLETE
QUESTIONS AND CORRECT ANSWERS (VERIFIED ANSWERS )
ALREADY GRADED A+
Assembly Occupancy's are buildings used for gathering of _____ or
more people for deliberation, worship, entertainment, eating, drinking,
amusement, awaiting transportation or similar. - ANSWER -50 people
Class 3 wiring installed under roof decking is required to be at least
__ inches below the roof decking - ANSWER -1.5 Inches
The minimum length of free conductors at outlet boxes is - ANSWER 6
Inches
A ________ ___ is required for each splice or termination point. -
ANSWER -Junction Box
Wiring inside ducts is not permitted unless - ANSWER -the wiring
applies to the direct functioning of the duct system.
Wiring or raceway installed in environmental air return spaces is
required to be ______ - ANSWER -Plenum rated.
The installation of wiring cannot impede the removal of - ANSWER
ceiling tiles
The Minimum size for EMT is - ANSWER -1/2 Inches
,The Maximum size of E.M.T is - ANSWER -4 Inches
E.M.T is required to have a maximum of ___ degrees of bends
between pull points - ANSWER -360
EMT is required to be secured ever __ feet - ANSWER -10
E.M.T is required to be secured withing _ feet of a box - ANSWER -3
E.M.T is _________ to be used as an equipment grounding donductor
- ANSWER -permitted.
Class 1 wiring is limited to ___ volts - ANSWER -600
Class 2 wiring is limited to ___ volts - ANSWER -150
Class 3 wiring is limited to __ volts - ANSWER -30
When located within _ feet of the floor FPL wire is required to be
protected - ANSWER -7
FPL circuit cable can be as small as __ gauge when using
multiconductor cable. - ANSWER -26
If an individual conductor is used as part of a FPL circuit, the
minimum conductor size is __ gauge - ANSWER -18
, FPL Fire alarm cable - ANSWER -This type of cable is suitable for
horizontal wire runs on a single floor. The plastic coating which
provides the insulation for the cable is flammable and produces a
toxic gas when burned.
FPLR Fire alarm cable (Riser) - ANSWER -This type of cable is
suitable for vertical wiring between floors. It is resistant to burning. It
produces a toxic gas when burned.
FPLP Fire alarm cable (Plenum) - ANSWER -This type of cable is
highest rated. FPLP cable is suitable for use in spaces used for
environmental air return. It does not produce toxic gas when burned.
What are permitted substitutions for FPL - ANSWER -CM, CMG, FLPR,
CMR, FPLP, CMP
What are permitted substitutions for FPLR - ANSWER -CMR, FPLP,
CMP
What are permitted substitutions for FPLP - ANSWER -CMP
The Americans with Disabilities Act was enacted in which year? -
ANSWER -1990
On a given floor of a building, manual pull boxes shall be located
such that no horizontal travel distance between pull boxes exceeds
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller nyagajoseph539. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $20.49. You're not tied to anything after your purchase.