Conductors that supply a single motor used in a continuous duty application shall have
an ampacity of not less that what percentage of the motor full-load current rating? -
1.25

EMT shall not be: - Threaded

Plug fuses shall be permitted to be used in circuits supplied by a system having
grounded neutral point where the line-to-neutral voltage doe NOT exceed which of the
following? - 150 volts

How many amperes does s a 3-hp, 240-volt, 3-phase motor draw if the motor has
values of 90% efficiency and 95% power factor? - 6.3 amperes

Where metallic plugs or plated used with nonmetallic enclosures, how far shall they be
recessed form the outer surface of the enclosure - 1/4"

Disregarding exceptions, what is the minimum size copper-clad aluminum
underground service conductor permitted? - 6 AWG

Information technology equipment shall be permitted to be connected to a branch
circuit by a power-supply cord with a maximum length of how many feet? - 15'

Unlisted nonconductive outside plant optical fiber cables shall not be permitted to be
installed in which type of raceways? - Flexible metal conduit

Which part of a bulk storage plant is classified as Class 2, Zone 2? - Drainage
ditches, separators and impounding basins

If installed and routed on the outside of a raceway, the length of the equipment
bonding jumper shall not exceed how many feet? - 6'

A circuit breaker does not have an interrupter rating shown on it. What is the
interrupter rating of this circuit breaker? - 5,000 amperes

What is the minimum size of the aluminum equipment grounding conductor where the
overcurrent protection ahead of a branch circuit or feeder is sized at 600 amperes? -
36557

The combined cross sectional area of all conductors or cables shall not exceed what
percent of the cross sectional are of the cell or header? - 0.4

, Power distribution blocks installed in boxes shall be - Listed

For permanently connected appliances, the branch-circuit overcurrent device shall be
permitted to serve as the disconnecting means for appliances rated at not over - 300
volt-amperes or 1/8hp

A metal underground water pipe used as grounding electrode shall be in direct contact
with the earth for a minimum of how many feet? - 10'

What is the minimum rating for a standard lampholder that shall be used for circuits
and equipment operating at less than 50 volts? - 660 watts

What is the minimum branch-circuit rating for ranges of 8-3/4 kW or more? - 40
amperes

Receptacles in residential units shall be installed such that no point measured
horizontally along the floor line of any wall space is more than how far from a receptacle
outlet? - 6'

Overcurrent protection for feeders and branch circuits supplying electric vehicle supply
equipment shall be sized for continuous duty and shall have a rating of not less than
what percentage of the maximum load of the electric vehicle supply equipment? - 1.25

What clearance must be maintained when the overhead spans of open conductors or
open multi-conductor cables of not over 1,000 volts, nominal, pass over residential
property? - 12'

Multiple nonmotor generator arc welders are being served by a branch panel. There
are two 120-amperes welders with a 70% duty cycle, one 90-amperes welder with a
80% duty cycle - 450 amperes

Which type of service-entrance cable has a flame-resistant and moisture resistant
covering? - Type SE

Exit signs, when required, shall have a lettering that is a minimum of how many inches
high? - 6"

High impedance grounded neutral systems in which a grounding impedance limits the
ground fault current to a low value shall be permitted for which type of system? - 3-
phase AC systems of 480 to 1,000 volts

In which locations are the installations of flexible metal conduit permitted? -
concealed locations

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller STUVATE. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $11.49. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

62890 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$11.49
  • (0)
  Add to cart