100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
MASTER ELECTRICIAN L QUESTIONS AND ANSWERS $10.99   Add to cart

Exam (elaborations)

MASTER ELECTRICIAN L QUESTIONS AND ANSWERS

 2 views  0 purchase
  • Course
  • MASTER ELECTRICIAL
  • Institution
  • MASTER ELECTRICIAL

MASTER ELECTRICIAN L QUESTIONS AND ANSWERS

Preview 2 out of 6  pages

  • August 23, 2024
  • 6
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • MASTER ELECTRICIAL
  • MASTER ELECTRICIAL
avatar-seller
GEEKA
MASTER ELECTRICIAN L QUESTIONS AND ANSWERS
An insulated grounding conductor of_____ or smaller shall be identified by a contiguous
white or gray outer finish or by three continuous stripes other than green insulation it's
entire length - Answers -8 AWG 200.6a

6" 210.6a - Answers -Equipment associated with the electrical installation can be
located above or below other equipment within their working space when the associated
equipment does not extend more than_____ from the front of the electrical equipment.

1 NYC 210.52 - Answers -How many receptacles are required within the perimeter of a
balcony deck or porch with a usable area of last and 20 ft.²

6 1/2 ' - Answers -The minimum headroom of working spaces about motor control
centers is _____ .

30 " / 6 1/2'. NYC 110.33 - Answers -At least one entrance to enclosures for electrical
installations shall not be less than _____ wide and _____ high shall be provided to give
access to the working space around your school equipment over 600 V nominal.

12'. 230.24b - Answers -What is the minimum height for a vertical overhead clearance
for a service drop conductor over a residential property and driveways with garage not
subject to truck traffic where a voltage does not exceed 300 V to ground.

4" 225.14 - Answers -Open conductors installed outside shall be separated from open
conductors of all the circuits or systems by not less than _____ .

8" NYC 450.42 - Answers -What is the minimum thickness of a transformer vault floor
made up with bricks or cement fill blocks ?

12 300.50 table note D - Answers -Underground service conductors that are not in case
in concrete and then I'll bury 30 inches or more below grade so I have their location
identified by a warning ribbon that is placed in the trench at least_____ inches above
the underground installation for 40 KV

125%. 430.22a - Answers -Branch circuit conductor that supply a single motor used in a
continuous duty application shall have an ampacity of not less than _____ percent of
the motors full load current

48 times. 314.71a - Answers -For Straight pulls , the length of a pull box shall not be
less than_____ Times the outside diameter,over the sheath, of the largest shielded or
lead covered conductor or cable entering the box on systems over 600 V

36 inches 408.18 - Answers -For switchboards that are not totally enclosed ,a space
of_____ or more shall be provided between toe top of the switchboard and any
combustible ceiling.

, 115%. 440.12 - Answers -A disconnecting means that serves a hermetic refrigerant
motor compressor , shall have an amp hour rating of at least_____ percent of the
nameplate rated load current or branch circuit selection current , which ever is greater

Shall Not be opened under load/ Isolating switches. 404.6/404.13 - Answers -Knife
switches rated for more than 1200 A at 250 V or less , and that over 600 A at 251 to 600
V , shall be used only as

CL2 and CL3. 725.179 - Answers -Class two and class three cables listed as suitable
for general purpose use , with the exception of risers ducts, plenums ,and other spaces
used for environmental air shall be type_____

3 inches. 410.68 - Answers -Branch circuit conductors within______ Of a ballast shall
have an insulation temperature rating not lower than 90°C or 194°F

#14 AWG. 800.100 - Answers -Communications circuits so I have a minimum grounding
conductor of______

Not allowed in NYC (because of EMT, otherwise 7'6"). 680.43b - Answers -When
mounting a light fixture supported by EMT over a hot tub protected by GFCI must have
a height of_____

6'. 680.22. 680.34 - Answers -When installing receptacles around the pool they should
be set back on the inside walls of not less than______

12 314.17( chart ) - Answers -How many number 10 conductors can be legally installed
in a 4 in. Square box 2 1/8 inch deep?

Separate branch circuit/ GFCI line side. 620.23. 620.24 - Answers -what kind of circuit
must the sump pump and lights in the elevator pit be connected to?

Copper insulated solid or stranded. NYC 800.100 (a)3 - Answers -When using a
grounding conductor it should not be smaller than #12 ______

5/7 NYC 110.2b 230.64 b - Answers -Where service equipment totaling 1000 kVA or
larger is installed separately or as part of a switchboard the room in which such
switchboard is located shall be constructed of non-combustible materials having a two
hour fire rating and should be of dimensions adequate to house the switchboard and to
provide the following minimum clearances. At least_____ feet in front of the switchboard
if is in one line and at least_____ feet in front of the board if boards are installed facing
each other.

12. 230.64 - Answers -Where service equipment totaling 1000 kVA or larger is installed
separately or as part of a switchboard the room in which such switchboard is located
shall be constructed of non-combustible materials having a two hour fire rating as

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller GEEKA. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $10.99. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

74735 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$10.99
  • (0)
  Add to cart