A 150 kVA service transformer has a 480Y/277 volt 3-phase primary and a 208Y/120
volt, 3-phase secondary. What is the approximate full-load ampere rating of the primary
of the transformer? - Answers -180 amperes
Where a conductor is marked RHW-2 on the insulation what does the "-2" represent? -
Answers -The conductor has a maximum operating temperate of 90 degrees C.
For a grounded electrical system supplied by a feeder or branch circuit, the equipment
grounding conductor shall be sized in accordance with _____. - Answers -the
overcurrent protective device
For lighting systems operating at 30-volts or less, the output circuits of the power supply
are to
be rated for NOT more than _____. - Answers -25 amperes
Using the standard method of calculation, what is the demand, in kW, on the
ungrounded (line) service-entrance conductors of an apartment complex that has thirty-
five (35) electric ranges rated at 11.5 kW each? - Answers -50 kW
Where a service riser is installed in a wet location and contains THWN insulated
conductors, the wiring method used _____. - Answers -is permitted to be electrical
metallic tubing (EMT)
What is the MAXIMUM distance between supports for straight horizontal runs of trade
size 1½ in. threaded rigid metal conduit (RMC)? - Answers -14 feet
Overcurrent protection of transformers, of 600 volts or less, is required to be sized
_____. - Answers -in accordance with Table 450.3(B)
A thermal barrier shall be required if the space between the resistors and reactors, of
600 volts or less, and combustible material is LESS than _____. - Answers -12 inches
What percent of electrical supplied RV spaces in a recreational vehicle park must have
50-ampere, 125/250-volt receptacle outlets provided? - Answers -20 percent
What is the MINIMUM bend radius of trade size 4 in. rigid metal conduit (RMC) where
the bend is not made with a one-shot or full-shoe bender? - Answers -24 inches
Type AC cable shall NOT be used _____. - Answers -where embedded in plaster in wet
locations
Where portions of a cable, raceway or sleeve are known to be subjected to different
temperatures and where condensation is known to be a problem, the raceway or sleeve
shall _____. - Answers -be filled with an approved material
, What is the MINIMUM size 75º C copper service-entrance conductors required for a 200
ampere rated commercial service? Assume ambient temperature and the number of
current-carrying conductors in the raceway is not a consideration. - Answers -3/0 AWG
THW
Two (2) or more motors may be installed without individual overcurrent protection
devices if rated less than 1 hp each, and the full-load current rating of each motor does
NOT exceed _____ if they are on a 120-volt, 20-ampere branch circuit. - Answers -6
amperes
Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be
cord-and-plug connected, provided the cord is NOT longer than _____ and protected by
a GFCI. - Answers -15 feet
In general, if a cablebus system is rated 95 amperes, the MAXIMUM allowable rating of
the overcurrent device used to protect the cablebus is _____. - Answers -100 amperes
A twenty-five (25) ft. long tap conductor tapped from a 100 ampere rated feeder
conductor, shall have an ampacity of NOT less than _____. - Answers -33.3 amperes
Disregarding exceptions, bonding between Class I locations and the point of grounding
for service equipment may be done by _____. - Answers -bonding jumpers
When an electrical service is required to have a grounded conductor present, what is
the smallest grounded conductor permitted for an electric service using size 1000 kcmil
copper ungrounded (phase) conductors? - Answers -2/0 AWG copper
A motel to be constructed will have two (2), 20-ampere, 120-volt branch circuits
provided for the exterior electric signs. Determine the demand load, in VA, for the
electric signs, on the feeder and service-entrance conductors. - Answers -3,000 VA
Luminaires shall be installed so that the adjacent combustible material is not subjected
to temperatures in excess of _____. - Answers -90 degrees C
An aluminum grounding electrode shall be _____. - Answers -prohibited
A panelboard is limited to 42 overcurrent protective devices where _____. - Answers -
the panelboard is a "split-bus" type panelboard
When rigid polyvinyl chloride conduit (PVC) is used to enclose conductors feeding a
wet-niche luminaire in a permanently installed swimming pool, a _____ insulated copper
grounding conductor shall be installed in this conduit, unless a listed low-voltage lighting
system not requiring grounding is used. - Answers -8 AWG
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller GEEKA. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $12.49. You're not tied to anything after your purchase.