Corrosion Specialist
✓ ~~> designs and certifies cathodic protection system
Secondary containment shall be constructed to contain at least the following
volumes:
✓ ~~> A. 100% of usable capacity of primary where there is only one
primary is within the secondary
B. 150% of the largest container if there are multiple primary containers in a
single secondary
Cathodic protection tester will test cathodic protection system within __
months of installation and every __ years thereafter
✓ ~~> 6 months
3 years
Spill container shall meet the following requirements:
Master01 | September, 2024/2025 | Latest update
, 2 | P a g e | © copyright 2024/2025 | Grade A+
✓ ~~> A. If made of metal, exterior wall shall be protected from galvanic
corrosion
B. Shall have minimum capacity of 5 gallons (19 L)
C. Shall have drain valve which allows drainage of the collected spill into the
primary container or provide means to keep spill cont empty
Overfill prevention shall alert transfer operator when tank is __% full
✓ ~~> 90%
Flapper Valves shall provide positive shut off when tank is filled to no more
than __% capacity
✓ ~~> 95%
Primary pressurized piping shall be tested for tightness hydrostatically at __%
of design operating pressure
✓ ~~> 150%
Date that all UST systems must have Line Leak Detector installed
✓ ~~> November 9,2004