propane practice tests with correct questions
according to the two permanent openings method one
room heaters shall not be installed in what occupa
define a type b w gas vent
Institution
PROPANE PRACTICE
Course
PROPANE PRACTICE
$15.49
100% satisfaction guarantee
Immediately available after payment
Both online and in PDF
No strings attached
PROPANE PRACTICE TESTS With Correct
Questions And Answers 2024
According .to .the .Two .Permanent .Openings .Method .one .opening .must .commence .within
.____ .and .one .must .commence .within .___ .of .the .enclosure .- .correct .answer.12 .inches .of
.the .top .12 .inches .of .the .bottom
Room .heaters .shall .NOT .be .installed .in .what .occupancies? .- .correct .answer.Health .care
.and .Residential .board .and .care.
Define .a .type .B-W .gas .vent: .- .correct .answer.It .shall .not .have .a .listed .capacity .NOT
.LESS .than .that .of .the .listed .vented .wall .furnace .to .which .it .is .connected.
Listed .vented .wall .furnaces .shall .use .which .type .of .venting .system? .- .correct
.answer.Type .B-W .gas .vent
NO .portion .of .a .venting .system .shall .extend .or .pass .through .any.... .- .correct
.answer.Fabricated .air .duct .OR .Furnace .plenum
The .exit .terminals .of .mechanical .draft .systems .shall .not .be .LESS .than .___________
.when .located .adjacent .to .public .walkways. .- .correct .answer.7 .ft .above .finished .ground
.level
Forced .draft .systems .and .all .portions .of .induced .draft .systems .under .positive .pressure
.during .operation .shall .be .designed .and .installed .so .as .to ._____________. .- .correct
.answer.Prevent .leakage .of .flue .gases .into .the .building
Mechanical .draft .systems .shall .be ._______ .. .- .correct .answer.Listed
A .chimney .for .residential .type .or .low .heat .appliances .shall .extend .at .least .2 .feet .higher
.than .any .portion .of .a .building .within .a .horizontal .distance .of ._______. .- .correct .answer.10
.feet
Category .I .Vented .appliance .- .correct .answer.An .appliance .that .operates .with .a .non-
positive .vent .static .pressure .and .with .a .vent .gas .temperature .that .avoids .excessive
.condensate .production .in .the .vent.
,Type .1 .and .Type .2 .clothes .dryers .shall .be .exhausted .to .the .________. .- .correct
.answer.Outside
Ventilating .hoods .and .exhaust .systems .shall .be .________ .installed .in .commercial
.applications .and .to .vent .industrial .equipment. .- .correct .answer.Permitted .to .vent .gas
.appliances
What .appliances .are .NOT .required .to .be .vented? .- .correct .answer.Counter .appliances .or
.Direct .gas-fired .make-up .air .heaters
What .is .the .correct .spacing .of .supports .for .3/4" .or .1" .steel .pipe? .- .correct .answer.Every .8
.feet
Regarding .indoor .combustion .air, .what .method .states .the .minimum .volume .shall .be .50
.cube .feet .per .1000 .Btu/hour? .- .correct .answer.Standard .method
All .dispensers .shall .be .installed .on .what .type .of .foundation? .- .correct .answer.Concrete
The .number .of .containers .in .a .building .undergoing .minor .renovations .shall .NOT .exceed
.the .________ .assigned .to .using .the .LP-gas. .- .correct .answer.Number .of .workers .and
.shall .not .exceed .______ .lbs .in .size
Aboveground .containers .shall .be .________. .- .correct .answer.Painted
All .regulators .for .outdoor .installations .shall .be .designed, ._______ .or .protected .so .that
.operation .will .not .be .affected .by .the .elements. .- .correct .answer.Installed
Temperature .sensitive .elements .of .emergency .shutoff .valves .shall .NOT .be .________ .. .-
.correct .answer.Painted
In .a .piping .system .where .condensation .of .vapor .can .occur, .piping .shall .be ._______, .or
.means .shall .be .provided .for .re-vaporizing .the .condensate. .- .correct .answer.sloped .back
.to .the .container
What .is .the .minimum .cover .that .should .be .maintained .over .all .underground .metallic
.piping? .- .correct .answer.12 .inches
Polyethylene .piping .systems .shall .be .limited .to .vapor .service .not .exceeding .________. .-
.correct .answer.30 .psig
A .listed .__________ .shall .be .installed .at .the .discharge .end .of .the .transfer .hose .at .vehicle
.fuel .dispensers. .- .correct .answer.Quick-acting .shutoff .valve
Metallic .pipe .joints .shall .be .permitted .to .be .____________ .using .proper .pipe .and .fittings.
.- .correct .answer.Welded .or .Brazed
, Flexible .metallic .connectors .shall .NOT .exceed ._________ .in .overall .length .when .used
.with .liquid .or .vapor .piping .on .stationary .containers .of .2000 .gallon .w.c. .or .less. .- .correct
.answer.5 .feet
Hose .length .at .a .motor .fuel .dispensing .station .may .NOT .exceed ._____________ .unless
.approved .by .AHJ. .- .correct .answer.18 .feet
Unlisted .air-conditioning .appliances .shall .be .installed .with .clearances .from .combustible
.material .of .NOT .less .than .____________ .above .the .appliance .and .at .the .sides, .front,
.and .rear. .- .correct .answer.18 .inches
The ._______ .employed .for .operating .the .automatic .main .gas .control .valve, .automatic
.pilot, .room .temperature .thermostat, .limit .control, .other .electrical .devices .used .with .the
.appliances .shall .be .in .accordance .with .the .wiring .diagrams .certified .or .approved .by .the
.original .appliance .manufacturer. .- .correct .answer.Electrical .circuit
The .sediment .trap .shall .be .installed .as .close .to .the .inlet .of .the .equipment .as .practical .at
.the .___________. .- .correct .answer.Time .of .equipment .installation
With .regard .to .the .indoor .use .of .nonmetallic .gas .hose .connectors, .an .equipment .shutoff
.valve .shall .be .installed .where .the .connector .is .________. .- .correct .answer.Attached .to
.the .building .piping
The .cross-sectional .area .of .the .common .vent .shall .be ._______________ .the .cross-
sectional .area .of .the .largest .connector. .- .correct .answer.Equal .to .or .greater .than
Appliances .and .equipment .shall .be .furnished .either .with .load .distributing .bases .or .with .a
.sufficient .number .of .________ .to .prevent .damage .to .either .the .building .structure .or .the
.appliance .and .the .equipment. .- .correct .answer.Supports
___________ .shall .be .located .so .as .NOT .to .interfere .with .proper .circulation .of
.combustion, .ventilation, .and .dilution .air. .- .correct .answer.Appliances
All .air .handled .by .a .non-circulating .direct .gas-fired .industrial .air .heaters .shall .be
.___________. .- .correct .answer.Ducted .directly .from .outdoors
Gas .piping .serving .heating .gas .appliances .shall .be .permitted .to .also .serve
._____________ .where .heating .and .cooling .equipment .cannot .be .operated
.simultaneously. .- .correct .answer.Cooling .equipment
Equipment .connected .to .a .piping .systemshall .have .an .accessible .approved .manual
.shutoff .valve .with .a .___________. .- .correct .answer.Non-displaceable .valve .member
Steam .and .hot .water .boilers, .shall .be .provided .with .approved .___________ .for .shutting
.down .the .burner .to .prevent .boiler .steam .pressure .exceeding .the .maximum .allowable
.working .pressure .or .temperature. .- .correct .answer.Automatic .limiting .devices