Review. Notification Appliances
Questions and Answers 2024
What can using a notification appliance outdoors that is not rated for outdoor use
cause? - answer Ground faults.
What requirements can mechanical covers or mechanical protection for notifications
appliance cause? - answer They may require derating of the appliance, reduced
spacing, and could cause reduced effectiveness of the appliance.
Where can installation instructions for notification appliances be found? - answer On the
product cut sheet.
Can a visual notification appliance that is only listed for wall mounting be used on a
ceiling? - answer No.
What type of audible appliance is used on an emergency voice/alarm communications
system? - answer Speaker.
What is an example of a textual audible device? - answerSpeaker
Can audible and visual appliances be wired on the same circuit? - answerYes. Textual
audible devices (speakers) must be on a separate circuit though as they require an
amplifier to provide the signal.
SPL (Sound Pressure Level) is measured in what scale? - answerA-weighted scale.
At what ambient SPL are visual notification appliances required? - answer105 dBa.
The minimum required SPL for public mode signaling is the greater of ____ above the
average ambient or five dB above the maximum SPL lasting a minute or more, using
the A-weighted scale (dBA). - answer15 dBa.
The minimum required SPL for private mode signaling is ____ above the average
ambient or five dB above the maximum SPL lasting a minute or more, using the A-
weighted scale (dBA). - answer10 dBa.