Where a one-family dwelling has a 200 amp, 120/240 volt, single phase main service panel and
is supplied with size 2/0 gauge THW copper ungrounded line service entrance conductors in
rigid metal conduit, the minimum required size of the ...
Journeyman Electrician Test With Solutions
100% Solved
Where a one-family dwelling has a 200 amp, 120/240 volt, single phase main service panel and
is supplied with size 2/0 gauge THW copper ungrounded line service entrance conductors in
rigid metal conduit, the minimum required size of the bonding jumper for this service entrance
conduit is _____ copper. 4 AWG
A disconnect switch enclosure installed in a Class 2, division 2, hazardous location in an
industrial establishment shall be ______. Dust-tight
The interior of enclosures or raceways installed underground shall be considered to be a _____
location. Wet
Determine the ampacity of four, size 1/0 gauge THW copper current carrying conductors
installed in a common raceway with an ambient temperature of 86 degrees Fahrenheit.
120 Amps
The NEC defines a continuous load to be a load where the maximum current on the circuit is
expected to continue for at least _____ hours or more. Three
, Journeyman Electrician Test With Solutions
100% Solved
Determine the minimum size THW copper branch circuit conductors the NEC requires to supply
a 3 phase, continuous duty, as motor that draws 70 amps per phase. Consider all terminations are
rated for 75 degrees celcius. 3 AWG
Given: You have determined a conductor has a computed ampacity of 75 amps. What is the
maximum standard amp rating of the overcurrent protection device the NEC permits to protect
this circuit here this is not a motor circuit or part of a multi-outlet branch circuit supplying more
than one receptical? 80 Amps
A 208 volt, 3 phase, 50 horsepower, squirrel cage, continuous duty, ac motor has a full load
running current rating of _____. 143 Amps
What is the maximum distance that a disconnect switch is permitted to be located from the
operator's station for a portable carnival ride? 6 feet
Determine the minimum trade size electrical metallic tubing (EMT) required to enclose eight, 6
guage AWG copper conductors with THHW insulation, when installed in a 50 foot conduit run.
1.25 inch
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller UpperClass. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $16.99. You're not tied to anything after your purchase.