1. A transaction of 100 MWs is scheduled out of your area at the top of the hour with a 10-
minute ramp.You have the following generation available
Whatcombination of generation would need to be used?
Generator Capacity Current MWs Ramp Capability1 100
MW 50 MW 5 MW/min
2 100 MW 40 MW 3 MW/min
3 100 MW 50 MW 1 MW/min
4 100 MW 60 MW 2 MW/min
Answer Generators 1, 2, 4
2. The Balancing Authority selling power to an end user entered the wrong schedule for
the upcoming hour. Which part of the ACE equation [ACE = (NIA
- NIS) - 10B (FA - FS) - IME], will cause Inadvertent Interchange to occur as theresult of the
1/8
1 of 23 10/8/2024, 8:29
,NERC Prep Test 2.pdf file:///C:/Users/HP/Desktop/New%20fl/NERC%20Prep%20Test%202
incorrect schedule?
Answer Both the Interchange portion and frequency portion of the Ace Equation will contribute
3. What is the most common cause of frequency fluctuations?
Answer System gener-ation and load imbalance
4. A Balancing Authority's inadvertent accumulation reflects over-generationduring on-
peak hours. When system load is decreasing, what actions could a Balancing Authority
system operator take to limit additional on peak inadver-tent accumulation?
Answer Decrease transactions into their system
Decrease generation
5. Balancing Authority A is currently reading a system frequency of 59.98 Hz. Its Net
Actual Interchange is +100 MW and its Net Scheduled Interchange is
+100 MW. If Balancing Authority A's frequency bias setting is 100 MW/0.1 HZ,what is
ACE?
Answer -20
2/8
2 of 23 10/8/2024, 8:29
,NERC Prep Test 2.pdf file:///C:/Users/HP/Desktop/New%20fl/NERC%20Prep%20Test%202
6. Governor droop is expressed as
Answer
A percentage of the frequency change required for a governor to move a unit from no load
to full load, or full load to noload
7. If the frequency bias setting is less negative than the frequency response of a
Balancing Authority and a frequency decline is caused by a sudden lossof generation in an
external balancing area, what will be the result?
Answer The ACEwill be positive value and AGC will lower generation
8. Which of the following combinations would represent the best generation control
performance (in terms of helping the Interconnection's frequency) bya Balancing Area?
Answer ACE is positive while frequency is below 60
9. If a Balancing Authority has an ACE of -175 MW and Frequency is 59.85 Hz.Which
real-time Control Performance Standard maybe outside of its lowlimit?
Answer BAAL
3/8
3 of 23 10/8/2024, 8:29
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller BESTGOODIES. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $12.49. You're not tied to anything after your purchase.