Answers
When the grounded conductor is to be spliced in a 12-inch by 12-inch junction box,
there shall be at least ? of free conductor left for splicing. - answer 6" (NEC 300.14)
When an outlet supplied through an underfloor raceway is removed, the sections of the
circuit conductors supplying the outlet shall be removed from the raceway. - answer
True (NEC 390.57)
A 4,160-volt feeder is to be installed in a nonmetallic conduit identified for direct burial
without concrete encasement. The minimum covering for the nonmetallic conduit is ?. -
answer 18" (NEC 305.15, Table 305.15(A))
Type SE service-entrance cable shall be permitted where the insulated conductors are
used for circuit wiring and the uninsulated conductor is used only for equipment
grounding purposes. - answer True (NEC 338.10(B)(2))
The radius of a bend in Type MI cable with an overall diameter of 1/2 inch shall not be
less than five times the external diameter of the cable measured ?. - answer to the
inner edge of the bend (NEC 332.24, 332.24(1))
Metal-clad cable shall be supported at intervals not to exceed ?. - answer 6' (NEC
330.30(C))
Type MI cable is required to be strapped at intervals not exceeding ?. - answer 6'
(NEC 332.30, 332.30(A))
In an installation of Type NM cable, the 90°C conductor ampacity rating shall be
permitted to be used for ampacity adjustment and correction calculations, provided that
the final calculated ampacity does not exceed that for a 60°C-rated conductor. - answer
True (NEC 334.80)
Which Chapter 3 article provides general requirements for wiring methods and
materials? - answer Article 300
Which Chapter 3 article covers requirements for cabinets, cutout boxes, and meter
socket enclosures? - answer Article 312
Which Chapter 3 article covers the requirements for electrical metallic tubing? - answer
Article 358