S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler test Spring 2024/2025
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO
DETERMINE QUALIFICATIONS. - -OWNER
-RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS. - -3
-THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH
REQUIREMENTS. - -IMPAIRMENT COORDINATOR
-REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________
FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - -1
-SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED
UNPLANNED OUT OF SERVICE CONDITIONS. - -1
-NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS. - -8
-FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL
IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT. -
-OWNER OF THE BUILDING
-IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - -30
-WHAT DOES "OOS" STAND FOR? - -OUT OF SERVICE
-OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT.
CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - -
TAGS
-A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE
AND ANY SECTIONAL VALVES. - -MASTER FIRE SUPPRESSION PIPING
CONTRACTOR
-__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND
FLOW PRESSURES BEFORE AND AFTER. - -DRAIN TEST RESULTS
-GREEN TAGS INDICATE THAT __________. - -NO IMPAIRMENT WAS FOUND
,-GREEN TAGS WILL BE PLACED ON THE ____________. - -MAIN CONTROL
VALVE
-SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________
TAG PLACED ON THE MAIN CONTROL VALVE. - -RED
-A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - -WHITE
-A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO
INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE. - -BLUE
-THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER,
CENTRAL STATION AND OCCUPANTS. - -INSURANCE
-PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE
THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED. - -IMPAIRMENT
COORDINATOR
-GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT
GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM
FREEZING. - -50, 40
-THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED
NEAR THE ____________. - -MAIN CONTROL VALVE
-__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE
FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - -
RECORDS
-FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND
COURT PROCEEDINGS. - -REVOCATION
-THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY
HOLD THE FOLLOWING CERTS: - -REFRIGERATION OPERATING ENGINEER,
HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE
OPERATING ENGINEER.
-A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE
AND SPRINKLER SYSTEMS. - -MASTER FIRE SUPPRESSION PIPING
CONTRACTOR (MFSPC)
-A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS. - -30
, -ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED
WHEN SPRINKLERS ARE INSTALLED. - -96
-WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING. - -40 FAHRENHEIT
-__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - -COLD
WEATHER
-________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE
HEATED TO PREVENT FREEZING. - -DRY PIPE
-THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. - -AIR
PRESSURE
-IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE
ALARM IS TRANSMITTED DIRECTLY TO THE _________. - -FIRE DEPARTMENT
-DRY PIPE VALVES ARE OF A ______ DESIGN. - -CLAPPER
-DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL
TRIP LEVEL. - -15-20
-AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO
ALLOW WATER INTO THE SYSTEM. - -REDUCE
-BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF
_______ PSI IS DETECTED IN THE SYSTEM. - -2
-IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE
SPRINKLER HEADS. - -PREACTION VALVE
-PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS
OPENED. - -VALVE
-THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP
DEVICES, RATE DEVICES, AND ___________ DEVICES. - -COMBINATION
-THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS
EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. - -RECYCLING
-THE ________ IN THE DELUGE SYSTEM ARE OPEN AT ALL TIMES. - -
SPRINKLER HEADS
-_________ SYSTEMS ARE USUALLY FOUND IN BASEMENTS OR OTHER
DIFFICULT TO REACH AREAS. - -PERFORATED PIPE
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller Victorious23. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $14.49. You're not tied to anything after your purchase.