1. The best tool for adjusting and setting the pressure on an appliance regu- lator:

a.
Manometer

b.
Velometer

c.
Psychrometer

d.
An analyzer: Manometer
2. 3/8 NPS black iron pipe shall?

a. Not be used for propane
b. Not be used in a concealed location
c. Not be used for natural gas
d. Not be used for indoors: Not be used in a concealed location (6.3.9)
3. A corrugated metal gas connector connected to a range must not exceed?

a. 6'
b. 5'
c. 3'
d. 4': 6' (6.21.3)
4. A manual shut-off valve shall be installed?

a. only on natural gas appliances
b. in either drop of riser of a residential appliance
c. downstream of the union
d. at the drip pocket: In either drop of riser of a residential appliance (6.18.2)
5. Black iron pipe 2 1/2 NPS at 150' long shall be pressure tested to?

a. The greater of 50psig or 1.5 times the maximum operation pressure for 180 minutes
b. 50 psig for 180 minutes
c. 1.5 times the maximum operation pressure for 180 minutes
d. 50 psig for 60 minutes: 50 psig for 60 minutes (Table 6.3)





, G2 Exam Prep

6. Buried piping or tubing shall be?

a. only copper type L coated, type G coated, type K uncoated
b. only copper type K, L or type G
c. schedule 50 ASTM A-53
d. only copper type L or G coated: Only copper type L coated, type G coated, type K
uncoated (6.2.7)
7. What is pressure drop?

a. The difference in the static pressure at the meter, and the working pressure at the
appliance regulator
b. The difference between the U tube manometer is the end that is open to the
atmosphere and the pressurized side when the appliance regulator is working
c. The difference between supply pressure and appliance manifold pressure when
the appliance calls for heat
d. The difference in the working pressure at the gas meter, and the working
pressure at the appliance regulator: The difference in the working pressure at the gas
meter, and the working pressure at the appliance regulator
8. Fittings used for steel piping may be made from?

a. brass or iron
b. copper to malleable iron
c. steel and plastic
d. malleable iron and steel: Malleable iron and steel (6.2.2)
9. Posts protecting piping and tubing entering a building from vehicular dam- age
shall be?

a. clearly marked and identified with yellow paint
b. Be spaced not more than 48" apart
c. Buried not less than 36" below grade
d. Made from 6x6 pressure treated wood: Buried not less than 36" below grade
(6.16.15)
10. The equivalent length of a 2 1/2 NPS forged tee is?

a. 9.25'
b. 12.4'
c. 15.3'
d. 10.3': 9.25' (Table A 16)



, G2 Exam Prep

11. What is the maximum horizontal spacing of supports for N.P.S. 1 1/4 inch gas
pipe?

a. 8'
b. 15'
c. 6'
d. 10': 10' (3m) (Table 6.2)
12. When gas piping enters a building, it must?

a. Enter above grade
b. Be taped, painted, and sleeved
c. Have a tracer wire
d. Enter below grade: Enter above grade (6.15.8)
13. When sizing a branch line, what is the minimum size of job fabricated
welding fittings that can be used on a NPS 6 gas supply header?

a. 2" NPS
b. 3/4" NPS
c. 3" NPS
d. 1/2" NPS: 3/4" NPS (6.8.8)
14. A dirt pockets shall be installed at the bottom of any piping or tubing, on the
final drop serving an appliance other than a(n)

a. Unit Heater
b. Furnace
c. Clothes dryer
d. Boiler: Clothes dryer (6.13.1)
15. Direct-vent wall furnace shall use what maximum length of corrugated metal
gas connector?

a. 6 ft.
b. 4 ft.
c. 8 ft.
d. 2 ft.: 2 ft. (6.21.3(c))
16. Every gas hose and gas fitting shall have a minimum working pressure of what.

a. 275 PSIG minimum or the setting of the hydrostatic relief valves.
b. 350 PSIG for piping and tubing operating at a container.



, G2 Exam Prep

c. 350 PSIG
d. 250 PSIG when connected to the outlet of a pump or compressor.: 350 PSIG (6.2.9)
17. What are the requirements for back filling underground piping or tubing?

a. It shall not have stones larger than 38 mm
b. The fill material shall contain no sharp objects.
c. A trench must be dug 15 inches deep
d. All of the choices: The fill material shall contain no sharp objects (6.15.6)
18. Question 17
What is the approximate purging time for NPS 1 that is 40 feet in length?

a. 7 Seconds
b. 28 Seconds
c. 14 Seconds
d. 43 Seconds: 28 seconds (Annex H Table H.1)
19. What is the maximum distance a readily accessible manual shut-off valve may be
installed from an appliance?

a. 2 ft. and identified
b. 10 ft. and identified
c. 25 ft. and identified
d. 50 ft. and identified: 50 ft. and identified (6.18.2(d))
20. What is the minimum unthreaded portion of a piping outlet required when
installing a gas piping through a floor for a range?

a. 2 Inches
b. 6 Inches
c. 3 Inches
d. 12 Inches: 2 inches (6.12.2)
21. When a high pressure test is required on a gas piping system, what type of
medium would you use to perform this test.

a. High Pressure gas
b. Static pressure using gas
c. Low pressure gas
d. Air or an inert gas: Air or an inert gas
22. Nesting of bushings is permitted

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller QuizMerchant. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $17.99. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

78861 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$17.99
  • (0)
  Add to cart