Assembly Occupancy's are buildings used for gathering of _____ or more people for deliberation, worship, entertainment, eating, drinking, amusement, awaiting transportation or similar. - CORRECT ANSWER 50 people
Class 3 wiring insta...
NICET Prep: Fire Alarms Exam
Questions Correctly Answered.
Assembly Occupancy's are buildings used for gathering of _____ or more people for deliberation,
worship, entertainment, eating, drinking, amusement, awaiting transportation or similar. - CORRECT
ANSWER 50 people
Class 3 wiring installed under roof decking is required to be at least __ inches below the roof decking -
CORRECT ANSWER 1.5 Inches
The minimum length of free conductors at outlet boxes is - CORRECT ANSWER 6 Inches
A ________ ___ is required for each splice or termination point. - CORRECT ANSWER Junction Box
Wiring inside ducts is not permitted unless - CORRECT ANSWER the wiring applies to the direct
functioning of the duct system.
Wiring or raceway installed in environmental air return spaces is required to be ______ - CORRECT
ANSWER Plenum rated.
The installation of wiring cannot impede the removal of - CORRECT ANSWER ceiling tiles
The Minimum size for EMT is - CORRECT ANSWER 1/2 Inches
The Maximum size of E.M.T is - CORRECT ANSWER 4 Inches
E.M.T is required to have a maximum of ___ degrees of bends between pull points - CORRECT ANSWER
360
,EMT is required to be secured ever __ feet - CORRECT ANSWER 10
E.M.T is required to be secured withing _ feet of a box - CORRECT ANSWER 3
E.M.T is _________ to be used as an equipment grounding donductor - CORRECT ANSWER permitted.
Class 1 wiring is limited to ___ volts - CORRECT ANSWER 600
Class 2 wiring is limited to ___ volts - CORRECT ANSWER 150
Class 3 wiring is limited to __ volts - CORRECT ANSWER 30
When located within _ feet of the floor FPL wire is required to be protected - CORRECT ANSWER 7
FPL circuit cable can be as small as __ gauge when using multi-conductor cable. - CORRECT ANSWER 26
If an individual conductor is used as part of a FPL circuit, the minimum conductor size is __ gauge -
CORRECT ANSWER 18
FPL Fire alarm cable - CORRECT ANSWER This type of cable is suitable for horizontal wire runs on a single
floor. The plastic coating which provides the insulation for the cable is flammable and produces a toxic
gas when burned.
FPLR Fire alarm cable (Riser) - CORRECT ANSWER This type of cable is suitable for vertical wiring
between floors. It is resistant to burning. It produces a toxic gas when burned.
FPLP Fire alarm cable (Plenum) - CORRECT ANSWER This type of cable is highest rated. FPLP cable is
suitable for use in spaces used for environmental air return. It does not produce toxic gas when burned.
What are permitted substitutions for FPL - CORRECT ANSWER CM, CMG, FLPR, CMR, FPLP, CMP
, What are permitted substitutions for FPLR - CORRECT ANSWER CMR, FPLP, CMP
What are permitted substitutions for FPLP - CORRECT ANSWER CMP
The Americans with Disabilities Act was enacted in which year? - CORRECT ANSWER 1990
On a given floor of a building, manual pull boxes shall be located such that no horizontal travel distance
between pull boxes exceeds _____________. - CORRECT ANSWER 200 Feet
Where specifically permitted, which occupancy type is exempt from audible notification requirements? -
CORRECT ANSWER Health Care
Which of the following terms are you not likely to come across, as it pertains to Building Rehabilitation?
- CORRECT ANSWER Removal
To be considered a Residential Occupancy, an apartment building must contain ______ or more dwelling
units. - CORRECT ANSWER Three
Automatic detection is required in Assembly Occupancies with loads greater than ____. - CORRECT
ANSWER 300
With a delayed egress locking system, the door must be immediately unlocked upon _____________. -
CORRECT ANSWER loss of power
What kind of Assembly Occupancy has its own subclassification and set of requirements? - CORRECT
ANSWER Carnival Funhouses
Which of the following is a component of Means of Egress? - CORRECT ANSWER Exit discharge
An occupancy does not fall into the DayCare classification under which of the following conditions? -
CORRECT ANSWER It is a daycare located in a church, which operates during Sunday morning services
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller Nursewendo. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $11.49. You're not tied to anything after your purchase.