The desired condensing temperature is 80 degrees to 98 degrees refrigerant R404A
control has cut in and cut out cut in is set at________Psig - ANSWER 230
Using an EPR to control space temperature with an R 22 system. desired space
temperature is 36 degrees
The EPR setting is________ psig - ANSWER 39
this control is used to operate a system if the condenser is located in a low ambient
space. - ANSWER automatic pump-down system
System R404A
Control type to control space temperature: Low-pressure control
Control has high event and low event
Space temp needs to range between 5 degrees and 0 degrees
High event would be set at_______ psig - ANSWER 38
This control is a mechanical control located in the suction line, it protects the
compressor from excessive suction pressure during hot box pull-down. - ANSWER
CPR
An R134A system with an adjustable high-pressure control manual reset type in
Raleigh Ne would have the cut-out set at_____psig - ANSWER 275
The desired condensing temperature is 80 degrees to 98 degrees
refrigerant R404A
control has cut in and cut out is set at________psig - ANSWER 175
Which of the following controls are operational only - ANSWER Headmaster
CPR
Sorit
, EPR
Fan cycle
The oil safety control should be the last power passing control in the control circuit
- ANSWER True
A fan cylce control is used to maintain________ in the winter time - ANSWER
High side pressure
An R22 system with an adjustable high-pressure control manual reset type in
Raleigh Ne would have the cut-out set at_______psig - ANSWER 380
The desired condensing temperature is 85 degrees to 104 degrees
refrigerant R404A
control has cut in and differential cut in is set at_____ psig - ANSWER 250
Which of the following controls are electromechanical only - ANSWER Fan cycle
Low pressure
Sorit
Oil failure
High pressure
You have and R22 system and a low ambient condition. It is using a fan cycle
control to contrgl highsids pressurg. I want to maintain my condensing temp
between 110 and 111 degrees F
Where would I set my cut in - ANSWER 230
This control is mechanical control located in high side of the system . It will stack
liquid in the condenser . It is adjustable - ANSWER ORI
This control is wired on the low side of the system and is a close on pressure rise. -
ANSWER Low pressure
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller luzlinkuz. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $11.49. You're not tied to anything after your purchase.