NCCER ELECTRICAL LEVEL 2 GROUNDING AND BONDING EXAM QUESTIONS WITH CORRECT ANSWERS
14 views 0 purchase
Course
NCCER Electrical
Institution
NCCER Electrical
NEC Article 250 - Answer-Is the primary governing article for the proper use and installation of grounding and bonding
short circuit - Answer-a conducting connection, whether intentional or accidental, between any of the conductors of an electrical system, whether it is from line-to-line or from...
NCCER ELECTRICAL LEVEL 2
GROUNDING AND BONDING EXAM
QUESTIONS WITH CORRECT ANSWERS
NEC Article 250 - Answer-Is the primary governing article for the proper use and
installation of grounding and bonding
short circuit - Answer-a conducting connection, whether intentional or accidental,
between any of the conductors of an electrical system, whether it is from line-to-line or
from line-to-neutral
Ground fault - Answer-as defined in NEC Article 100, is an unintentional, electrically
conducting connection between an ungrounded conductor of an electrical circuit and the
normally noncurrent-carrying conductors
equipment grounding conductor - Answer-the conductive path used to connect the
noncurrent-carrying metal parts of equipment, raceways, and other enclosures to the
system grounded conductor, the grounding electrode conductor, or both.
Grounding systems less than 50v - Answer-grounding is required in the following
situation where supplied by transformers if the supply voltage to the transformer
exceeds 150v to ground
Grounding AC systems over 1kV - Answer-must be grounded if they supply mobile or
portable equipment as covered in NEC Section 250.188
5A ( 50-45=5) - Answer-a single phase system has two legs, Leg A and Leg B. Leg A is
carrying 50A and leg B is carrying 45A, the current carried by the neutral is what
-Lightning,
-voltage surges higher than that for which the circuit is designed - Answer-a grounded
system must limit the voltage on the electrical system and protect it from
Grounding electrode system - Answer-In general, all the following electrodes that are
present must be bonded together to form
steel or iron must be at least 1/4" thick
copper need only be 0.06" (1.5mm) thick - Answer-how thick must plates of iron or steel
how thick must nonferrous metal like copper be
20 ohms or less - Answer-Rod, pipe, and plate electrodes must have a resistance to
ground of__. If not, they must be augmented by an additional electrode spaced not less
than 6' from the first
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller lectknancy. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $9.49. You're not tied to anything after your purchase.