The efficiency of the refrigerant cycle is affected by the operation of the condenser. of the following. a more efficient centrifugal compressor operation results from: - Correct Answer Lowering the condensing pressure The heat removed from the refrigerant in a condenser is: - Correct Answer ...

[Show more]

Preview 3 out of 21  pages

  • October 2, 2024
  • 21
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • FDNY Z51
  • FDNY Z51
avatar-seller
Victoria108
FDNY written z51 questions And Complete
Solutions 2024/25
The efficiency of the refrigerant cycle is affected by the operation of the condenser. of the following. a
more efficient centrifugal compressor operation results from: - Correct Answer Lowering the
condensing pressure



The heat removed from the refrigerant in a condenser is: - Correct Answer Sensible and latent heat



The refrigerant unit that you have been assigned to is being taken out of service for a major repair. you
have been assigned to withdraw refrigerant for storage in suitable containers. according to the new York
city fire code, you must ensure that the containers: - Correct Answer Are approved by the US
department of transportation



Which of the following best describes how the cylinder unloader work? - Correct Answer Keep in the
suction valve opened while the compressor is in the return stroke



In most semi hermetic compressors, the suction vapor is used to: - Correct Answer Cool the motor



The amount of refrigerant that flows through the orifices of a economizer is determined by the: - Correct
Answer Difference between the high side and load side pressure



The installation of an inline refrigerant cleaning system is advisable: - Correct Answer To remove
impurities from the system



The type of refrigerant system that is least likely to leak refrigerant into the building space that are
cooled - Correct Answer The indirect system



The suction pressure of a reciprocating compressor is 65PSIG. the discharge pressure of this compressor
is 120PSIG. the atmospheric is 14.7 PSI. the compression ratio for the given condition is closet to: -
Correct Answer 1.69

,A super heated vapor is a ? - Correct Answer Dry vapor above the saturation temperature



A refrigerant engineer verifies that a condenser water pump is cavitating. of the following the most likely
cause for this condition is: - Correct Answer A faulty cooling tower water level controller



A centrifugal water pump is known as a lift pump when the: - Correct Answer The water supply to the
pump suction inlet is below the pump level



A TXV is used to maintain constant: - Correct Answer Evaporator superheat



The chilled water supply to the building is 55F. if the chiller is being used for human comfort, should you
be concerned about this , and why? - Correct Answer Yes, this temperature is too high for human
comfort purpose



The packing gland of a centrifugal pump serves to: - Correct Answer The drip part of the packing gland
gives evidence that there is water in the pump



Capacity control of a reciprocating hermetic compressor is typically achieved through - Correct Answer
Operation of the hot gas bypass valve



The most important reason to sub-cool the refrigerant in the condenser is to ensure that: - Correct
Answer A pure liquid refrigerant will enter the metering device



A refrigeration engineer is logging reading from a reciprocating system. compressor discharge
temperature have dropped significantly and the suction line pressure is high. which of the following that
may be causing this set of condition. - Correct Answer An expansion valve that is open to wide



A low side float valve is used to maintain: - Correct Answer The level of the refrigerant in the evaporator



Regarding fire safety, which ASHARE refrigerant safety classification indicates no flammability and lower
the toxicity? - Correct Answer A1

, When an expansion valve is operating properly, at the end of the evaporator will contain: - Correct
Answer Only superheated vapor



What information is not contained in a material safety data sheet-MSDS? - Correct Answer Cost of
material



In a steam turbine, what is the function of the kingsbury thrust bearing - Correct Answer Maintain axial
positioning of the rotor shaft



A centrifugal water pump is considered to be fully primed when - Correct Answer The pump is full of
liquid



Copper tubing refrigerant lines must be installed for a new system. it is a well known service practice
that tubing collapses at bends that must be made, the refrigerant engineer should use - Correct Answer
Lever type tubing bender



A reciprocating compressor is making a knocking sound during operation. if the refrigerant worn parts
are not causing the knocking, what is probably the cause - Correct Answer The slugging of the liquid
refrigerant



In order for a refrigerant to become superheated in a section of the lowside refrigerant line: - Correct
Answer Where no liquid refrigerant is present



All liquid has been recovered from a system to be overhauled, the system - Correct Answer Should not
be opened until all vapor has been removed



When a refrigerant engineer uses a portable compressor recovery unit to remove vapor refrigerant from
a refrigeration system the removal rate of the refrigerant will gradually slow down because - Correct
Answer The vapor density is decreasing



You are the engineer running a 2000-ton (steam-driven turbine) centrifugal refrigeration system, a
refrigeration system supplies chilled water to a college campus with multiple buildings. During the course
of making your rounds, you check the 9 cell cooling tower on the roof. You note the water level in all of

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller Victoria108. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?