ICC Bolting Exam 2024 | Structural Steel
and Bolting Exam Latest 2024 Questions
and Correct Answers Rated A+
According to the IBC, the "blank" is to hire the special inspector. -
ANSWER-owner or owners agent. 2009 IBC Section 1704.1
According to the IBC, the "blank" is the responsible for the approval of
a person's qualifications to act as a special inspector. -ANSWER-code
official. 2009 IBC, Section 1704.1
According to the IBC, discrepancy corrections are made known to the
building official by: -ANSWER-final report. 2009 IBC, Section1704.1.2
When is the code official to be made aware of a discrepancy found
during a special inspection? -ANSWER-If it is not corrected by the
contractor. 2009 IBC, Section 1704.1.2
According to the Model Program for Special Inspection, the special
inspector is to document work that is nonconforming: -ANSWER-In a
written report - Section II B 4 - Model Programs
According to the Model Program for Special Inspection, the special
inspector is to prepare written report of inspection: -ANSWER-After
each inspection visit - Section II B 5 - Model Programs
According to the Model Program for Special Inspection, which of the
following items does not need to be included in each inspection
report? -ANSWER-Description of discussions with the contractor -
Section B 5 - Model Programs
According to the Specification for Structural Joints using high strength
bolts, the nominal diameter of standard bolt holes shall be how much
larger than the nominal bolt diameter? -ANSWER-1/16 inch -
Specification for Structural Joints Table 3.1
,Discrepancies in the work shall be brought to the immediate attention
of the "blank" for corrective action. -ANSWER-the contractor - 2009
IBC, Section 1704.1.2.
The special inspector shall furnish inspection reports to the "blank"
and to the "blank"? -ANSWER-Building Official and Registered Design
professional
The special inspector shall provide continuos inspection of: -
ANSWER-Single-pass fillet welds greater than 5/16 inch in size - 2099
IBC, Table 1704.3, Item 5.3
The special inspections required by this code are not required where
the work is done on the premise of a? -ANSWER-Approved fabricator
- 2009 IBC, Section 1704.2.2
The special inspection of the steel fabrication process shall not be
required where the fabricator does not perform any? -ANSWER-
heating operations - 2009 IBC, Section 1704.3, Exceptions # 1
According to the Specifications for Structural Steel Buildings, ASTM
Standard "blank" is to be used for the material test for steel sheets. -
ANSWER-A568 - Section A31, Specifications for Structural Steel
Buildings
According to the Specifications for Structural Steel Buildings, the
"blank" conducts the material tests for identification of the structural
steel. -ANSWER-Fabricator or Testing Laboratory - Section A31,
Specifications for Structural Steel Buildings.
According to the Specifications for Structural Steel Buildings, which of
the following steel members are allowed to be unidentified steel? -
ANSWER-Unimportant members, where their physical properties and
weldability would not affect the structure strength - Section A31b,
Specifications for Structural Steel Buildings
,According to the Code of Standard Practice for Steel Buildings and
Bridges, how is steel of special material to be identified? -ANSWER-It
is marked by the supplier - Section 5.1.1, Code of Standard Practice
for Steel Buildings and Bridges
According to the Code of Standard Practice for Steel Buildings and
Bridges, how are fabricators stock steel material identified? -
ANSWER-Certified mill test reports - Section 5.2.2 - Code of Standard
Practice for Steel Buildings and Bridges
According to the Specification for Structural Steel Buildings, what
ASTM Standard would apply to a sample for structural steel pipe? -
ANSWER-A53 - Section A31a - Specification for Structural Steel
Buildings
According to the Code of Standard Practice for Steel Buildings and
Bridges, the number of samples required to be tested for structural
steel is: -ANSWER-The number specified by the ASTM specification -
Section 5.1.1 - Code of Standard Practice for Steel Buildings and
Bridges
According to the Specification for Structural Steel Buildings, which
ASTM standard would apply to a sample for structural steel plates? -
ANSWER-A36, A283, and A242 - Section A31a - Specification for
Structural Steel Buildings
According to the Specification for Structural Steel Buildings, "blank"
tests are required for samples for built-up sections consisting of plates
over 2 inches in thickness. -ANSWER-Charpy V-notch testing -
Section A31d, Specification for Structural Steel Buildings
According to the Specification for Structural Steel Buildings, ASTM
standard "blank" would apply to a sample for structural steel bars. -
ANSWER-A36, A529, and A572 - Specification for Structural Steel
Buildings
, Steel furnished for structural load-carrying purposes shall be properly :
-ANSWER-Identified - 2009 IBC, Section 2203.1
Steel that is not readily identifiable as to grade by marking and test
records shall be: -ANSWER-tested - 2009 IBC, Section 2203.1
Where materials or assemblies are required by this code to be
labeled, such material and assemblies shall be labeled by: -ANSWER-
An approved agency - 2009 IBC, Section 1703.5
Inspection of the steel frame for compliance with the approved
construction documents should verify: -ANSWER-Member location,
Bracing, and Stiffening - 2009 IBC, Section 1704.3.2.
Continuous inspection of bolt pre-tensioning is required when using: -
ANSWER-The calibrated wrench method - 2009 IBC, Section
1704.3.3.3.
Where required by the code, the building owner shall employ a
registered design professional to perform: -ANSWER-Structural
Observation - 2009 IBC, Section 1709.1
According to the Specification for Structural Joints, how does the
special inspector verify the bolts, nuts, and washers meet the
requirements of A325 or A490 specifications? -ANSWER-
Manufacturer certification - Section 2.1 - Specification for Structural
Joints
According to the Specification for Structural Joints, how are the high-
strength bolts, nuts, and washers to be stored at the job site? -
ANSWER-In a protected shelter in closed containers - Section 2.2 -
Specification for Structural Joints
According to the Specification for Structural Joints, how does the
special inspector determine the type of high-strength bolts that are to
be used for a project or particular bolt joints? -ANSWER-The engineer