100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
Load Calculations Branch And Feeder Circuits: Questions With Solutions $17.99   Add to cart

Exam (elaborations)

Load Calculations Branch And Feeder Circuits: Questions With Solutions

 0 view  0 purchase
  • Course
  • LOAD CALCULATIONS
  • Institution
  • LOAD CALCULATIONS

Load Calculations Branch And Feeder Circuits: Questions With Solutions

Preview 3 out of 20  pages

  • November 7, 2024
  • 20
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • LOAD CALCULATIONS
  • LOAD CALCULATIONS
avatar-seller
LeCrae
Load Calculations Branch And Feeder Circuits:
Questions With Solutions

Maximum load that may be supplied by 20a, 120v circuit? Right Ans - 20a x
120v = 2400va

Maximum load that may be supplied by 20a, 3 wire, 120/240v circuit?
Right Ans - 20a x 240v = 4800va

Maximum load that may be supplied by 20a, 208v 3 phase circuit? Right
Ans - 20a x 208v x 1.732 = 7205.12va

Minimum size circuit breaker required for 9 florescent ballast rated at 1.5a at
120v, as a continuous load? Right Ans - determine branch circuit load
9 x 1.5a = 13.5a

Determine the continuous duty load
13.5a x 1.25 = 16.88a

Minimum breaker size is 20a

How many receptacle outlet devices in other than residential occupancies can
be connected to a 20a, 120v circuit? Right Ans - determine branch circuit
capacity
20a x 120v = 2400va

NEC section 220.14.i each outlet is assigned a lad of 180va so
2400va / 180va = 13.33 or 13 receptacle outlets

What is the minimum size branch circuit required to serve a 17a, 120v copy
machine? Right Ans - nec sections 210.23a1 and b, the rating of any one
cord connected utilization equipment shall not exceed 80% of the branch
circuit rating.

30a x 0.8 = 24a so the minimum size circuit is 30a

,Maximum lighting load connected to a 20a circuit supplying equipment with a
rating of 8.5a, 120v? Right Ans - 20a - 8.5a = 11.5, the equipment load is
only 50% of the circuit rating so 11.5% may be added.

minimum size branch circuit required to supply a 14.7a, 208v, 3 phase,
continuous load restaurant dishwasher? Right Ans - 14.7 x 1.25 = 18.38a,
so 20a is the minimum

derated ampacity for each of 8, no.12 thhn wire in a single conduit? Right
Ans - 310.15b16 ampacity is 30a
310.15b3a adjustment factor is 70%

70% or 30a = 30a x 0.7 = 21a

maximum load connected on each of 6, no.2 thwn wires in a single conduit?
Right Ans - 310.15b16 ampacity is 115a
310.15b3a adjustment factor 80%

80% of 115a = 155a x 0.8 = 92a

the ambient temp. in a room is 92f (33.3c) minimum size thhn wire to supply
equipment? Right Ans - 310.15b16 ampactiy is 75a
310.15b3a adjustment factor 0.96

75a x 0.96 = 72a is no.6 thhn is required

minimum size wire and over current protection device required for a 16a
circuit of continuous loads, with 12 thhn in a raceway with an ambient temp.
of 105f? Right Ans - 210.19a1 conductors
210.20a overcurrent

16a x 1.25 = 20a for a continuous load

310.15b3a adjustment factor 50%
20a / 0.50 = 40a

310.15b2a ambient temp. adjustment
40a / 0.87 = 45.98a

, 310.15b16 no.8 thhn on a 20a ocpd



will 95' of no.12, 120v, 14.5a, non-contiuous load, exceed 3% voltage drop?
Right Ans - chapter 9, table 8 no.12 resistance is 1.93 ohms
vd =2 x L x r x i / 1000
vd = 2 x 95' x 1.93 x 14.5a / 1000
vd = 5.32

divide by 120v to find percentage
5.32v / 120v = 0.0443
0.0443 x 100 = 4.43% so yes it will exceed the 3% allowed

size thhn recommended for a non-contiuous load with 130' of single phase,
23a, 240v? Right Ans - vd = 2 x L x r x i / circular mils
vd = 2 x 130' x 12.9 x 23a / 10380 no.10 wire
vd = 7.43v / 240 = 0.031
0.031 x 100 =3.10%

need to size up to no.8 wire

size thhn wire is recommended for a 240v, 3 wire circuit with 3 fixed 240v
loads of 30a at 60', 30a at 80', and 20a at 100'? Right Ans - determine load
center length
60' x 30a = 1800
80' x 30a = 2400
100' x 20a = 2000
sum of loads = 80a
sum of products = a = 77.5 load center length

310.15b16 no. 4 thhn wire for 80a is selected, now check for voltage drop

vd = 2 x L x k x I / cm
vd = 2 x 77.5' x 12.9 x 80a / 41740
vd = 3.8v
240 x 3% = 7.2v so no.4 wire is permissible

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller LeCrae. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $17.99. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

82215 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$17.99
  • (0)
  Add to cart