S12 Certificate of Fitness Sprinkler Exam Study Guide Solutions Updated 2024 Buildings (4.1.1.1) - Shall be inspected (how often) the building owner shall ensure that all areas of the building containing water-filled piping shall be maintained at a minimum temperature of 40°F and not exposed t...

[Show more]

Preview 4 out of 107  pages

  • November 17, 2024
  • 107
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • S-12 S-13 Standpipe and Sprinkler
  • S-12 S-13 Standpipe and Sprinkler
avatar-seller
SophiaBennett
S12 Certificate of Fitness Sprinkler Exam
Study Guide Solutions Updated 2024

Buildings (4.1.1.1) - Shall be inspected (how often) the building owner shall ensure that

all areas of the building containing water-filled piping shall be maintained at a

minimum temperature of 40°F and not exposed to freezing conditions - ANSWER✔✔-


When the pump is in operation a small water leak on the pump bearings is desirable

and should not be considered a malfunction. Additionally, water should discharge from

a ---- relief valve (electric pump) or --- exchanger (diesel pump) while the fire pump is

operating under a "no-flow" condition. - ANSWER✔✔-circulation /heat


A sprinkler system is a - ANSWER✔✔-fire extinguishing system, other than a water

mist system, that utilizes water as the extinguishing agent.


Inspection, testing, servicing and other maintenance of sprinkler systems must be -

ANSWER✔✔-personally supervised and be performed in accordance with NFPA

(National Fire Protection Association) #25 2011 edition.


All multiple dwellings, factories, office buildings, warehouses, stores and offices,

theaters and music halls, hospitals and asylums, and all public schools and other public

buildings, churches and other places where large numbers of persons are congregated

for purposes of worship, instruction, amusement, and all piers, bulkheads, wharves,

Copyright ©SOPHIABENNETT 2025 ACADEMIC YEARALL RIGHTS RESERVED. Page 1/107

,pier sheds, bulkhead sheds or other waterfront structures shall provide - ANSWER✔✔-

fire extinguishers, buckets, axes, fire hooks, fire doors and other means of preventing

and extinguishing fires as the commissioner may direct.


Required fire protection systems shall be extended or altered as necessary to maintain

and continued protection whenever - ANSWER✔✔-the building or structure is altered.

Systems not complying with this section shall be considered to be impaired.


It shall be unlawful to install or maintain any fire protection system or device that has -

ANSWER✔✔-the physical appearance of fire protection equipment but that does not

perform a fire protection function where it may be confused with actual fire protection

equipment. An example would be a CCTV camera that is installed inside a shell that

resembles a sprinkler head


SPRINKLER AND/OR STANDPIPE SYSTEM MAINTENANCE AND INSPECTIONS -

ANSWER✔✔-


1. Automatic and non-automatic sprinkler systems shall be inspected, tested and

maintained as required by NFPA #25 2011 edition by a competent person holding a S-

12 Certificate of Fitness and employed or contracted by the owner, to see that all parts

of the system are in good working order, and that the Fire Department connection(s), if

any, are ready for immediate use by the Fire Department. A detailed record shall be

kept on the premises or other approved location, for a minimum of 3 years for

examination by any representative of the Fire Department. - ANSWER✔✔-


Copyright ©SOPHIABENNETT 2025 ACADEMIC YEARALL RIGHTS RESERVED. Page 2/107

,2.A supply of at least six extra sprinkler heads shall be kept available on the premises,

to replace promptly any fused or damaged sprinklers. Any head which has opened or

has been damaged shall be replaced immediately with sprinkler head of similar

characteristics such as operating temperature, orifice size, deflector orientation and

thermal sensitivity. - ANSWER✔✔-


3. At least once every five years, the Fire Department connection or connections for a

sprinkler system shall be subjected to a hydrostatic pressure test to demonstrate its

suitability for Fire Department use. The test shall be arranged to be conducted by a

Master Fire Suppression Piping Contractor in the presence of a Fire Department

representative.


The contractor shall be hired by the owner or the owner's representative. -

ANSWER✔✔-


4.There shall be one or more employees or individuals contracted by the owner with a

Certificate of Fitness to inspect the sprinkler system following the standard of the NFPA

25 of 2011. - ANSWER✔✔-


Automatic and non-automatic sprinkler systems shall be inspected, tested and

maintained as required by NFPA #25 2011 edition by - ANSWER✔✔-competent person

holding a S-12 Certificate of Fitness and employed or contracted by the owner, to see

that all parts of the system are in good working order, and that the Fire Department

connection(s), if any, are ready for immediate use by the Fire Department.


Copyright ©SOPHIABENNETT 2025 ACADEMIC YEARALL RIGHTS RESERVED. Page 3/107

, A detailed record shall be kept on the premises or other approved location, for a

minimum of - ANSWER✔✔-3 years for examination by any representative of the Fire

Department.


A supply of at least----extra sprinkler heads shall be kept available on the premises, to

replace promptly any fused or damaged sprinklers. - ANSWER✔✔-6


Any head which has ----or has been----1. shall be replaced immediately with sprinkler

head of similar characteristics such as operating temperature, orifice size, deflector

orientation and thermal sensitivity. - ANSWER✔✔-opened/damaged


At least once every ---- years - ANSWER✔✔-Fire Department connection or connections

for a sprinkler system shall be subjected to a hydrostatic pressure test to demonstrate its

suitability for Fire Department use.


At least once every five years, the Fire Department connection or connections for a

sprinkler system shall be subjected to a hydrostatic pressure test to demonstrate its

suitability for Fire Department use. The test shall be arranged to be conducted by a ----

by a----The contractor shall be hired by----- - ANSWER✔✔-Master Fire Suppression

Piping Contractor/1. a Fire Department representative/the owner or the owner's

representative.


There shall be---more employees or individuals contracted by the owner with a----

Certificate of Fitness 1. inspect the sprinkler system following the standard of the NFPA

25 of 2011. - ANSWER✔✔-one/COF

Copyright ©SOPHIABENNETT 2025 ACADEMIC YEARALL RIGHTS RESERVED. Page 4/107

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller SophiaBennett. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $13.49. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

67163 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$13.49
  • (0)
  Add to cart