According to CCR, Title 23 UST Regulations, What is the frequency that the Monitor Certification must be
performed? - CORRECT ANSWER-Every 12 Months
If visual monitoring is utilized as the means of release detection for single walled tank, it must be
conducted on a _______ Basis. - CORRECT ANSWER-Daily
The Purpose of spill and overfill protection equipment is to minimize the potential for a release during: -
CORRECT ANSWER-Fuel Deliveries
Which of the following is a potential symptom of toxic petroleum exposure: - CORRECT ANSWER-
Dizziness
Tremors
Eye irritation
All of the above(correct)
Under-Dispenser Containment is required for ______ underground storage tank systems - CORRECT
ANSWER-All
All of the following are true for Automatic Tank Gauging (ATG) except for: - CORRECT ANSWER-ATG
system are required to be installed in all UST system
According to CCR Title 23, UST regulations Spill containment (spill bucket) must meet all of the following
requirements except: - CORRECT ANSWER-Be installed on vent risers
Suction piping may not require leak detection if it has one check valve located where? - CORRECT
ANSWER-Directly below the suction pump
ICC Service Technician Study Guide Questions & Answers
,Service Technician performing work on Monitoring equipment must be trained and certified by
__________ - CORRECT ANSWER-The manufacture of the equipment.
Air monitoring must be conducted ________ when performing work within a confined space. - CORRECT
ANSWER-Prior to and during
A UST Service Technician must be recertified by the equipment Manufacture at the time interval
recommended by the equipment manufacture or at least every ____ months, whichever is greater. -
CORRECT ANSWER-36 Months
When an automatic tank gauge is utilized for single-walled tank leak detection, it shall test the tank at
least monthly after product delivery or when the tank is filled to within _____ percent of the highest
operating level during the previous month. - CORRECT ANSWER-10
The following is true of spill buckets except: - CORRECT ANSWER-Must provide drainage for spilled
product into the secondary containment sump.
If during an inspection of dispensing equipment at a retail gas station you find that the product is
dispensing at a significant lower rate than usual. You should check: - CORRECT ANSWER-For piping leaks.
According to CCR title 23, UST Regulations the local agency must be notified by the Owner/Operator
how long before conducting Secondary Containment Testing? - CORRECT ANSWER-At least 48 hours
before the test.
Poppet Valves are a Vapor Recovery Component installed: - CORRECT ANSWER-on the vapor recovery
riser
If equipped with an ATG it shall be programmed to test the tank _______? - CORRECT ANSWER-at least
monthly
A Vacuum-assist nozzle is a component of a(n) ________? - CORRECT ANSWER-Stage II vapor recovery
system
ICC Service Technician Study Guide Questions & Answers
, Stage I Vapor Recovery can be installed in the following configured(s): - CORRECT ANSWER-Dual Point,
Manifold, & Coaxial
An Underground tank System includes: - CORRECT ANSWER-The underground storage tank
Piping
Ancillary Equipment
All of the above is correct
If equipped with an overfill alarm, the alarm must be triggered to alert the delivery operator when the
tank is no more than _______ full. - CORRECT ANSWER-90%
Approved Cathodic Protection Methodologies include: - CORRECT ANSWER-Sacrificial Anodes, &
Impressed current system
_________is a system for exchanging gasoline vapors in a storage tank(s) and product in a fuel delivery
truck. - CORRECT ANSWER-Stage I Recovery
Automatic Line Leak Detectors, installed on Underground Piping with Secondary Containment. Shall be
capable of detecting a leak of _______ at 10 PSI. - CORRECT ANSWER-3 gallons per hour (GPH)
The fastest exposure for Petroleum Toxicity to affect the body is through: - CORRECT ANSWER-
Inhalation (Through breathing)
According to California Health and Safety Code for Underground Storage of Hazardous substances, An
"underground storage tank" is defined as: - CORRECT ANSWER-An underground tank and connecting
piping.
For existing UST's using Automatic tank Gauges as the sole means of quantitative release detection, the
ATG, must be capable of detecting a release of ______ gallons per hour. - CORRECT ANSWER-0.2 GPH
In case of gasoline, it is the _______ that pose(s) a threat of combustion. - CORRECT ANSWER-Vapors
ICC Service Technician Study Guide Questions & Answers
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller Lectphilip. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $15.49. You're not tied to anything after your purchase.