IEC 3A TEST BANK QUESTIONS AND CORRECT ANSWERS (VERIFIED ANSWERS) ALREADY PASSED When an isolated ground receptacle is installed in a metal box, a(n) ___ equipment grounding conductor is required for connection to the metal box. Select one: ate copper ized ated - 2020 NEC: 250.96(B) The correct answer is: separate The equipment grounding conductor is permitted to be run separately from the circuit conductors when ___. Select one: lled in industrial establishments only equipment grounding conductor has the same insulation as the circuit conductors c.a nongrounded-type receptacle is replaced branch circuit is less than 30 amperes - 2020 NEC: 250.130(C) The correct answer is: a nongrounded-type receptacle is replaced Which of the following receptacles are required to be GFCI protected? I. where installed in a patient's room in a hospital II. where installed on the exterior wall (outdoors) of an elementary schoolIII. where installed adjacent to (2 feet away from) a sink in a bar - 2020 NEC: 210.8(B)(4) | 2020 NEC: 210.8(B)(5) The correct answer is: II & III only Which of the following receptacles are required to be GFCI protected?I. where installed outside on the exterior wall of a restaurantII. where installed on the wall at 18" AFF (NOT above a countertop) in the kitchen at a restaurantIII. where installed on the exterior wall (outdoors) of an elementary school Select one: a.II only b.I, II & III c.I only d.II & III only e.III only - 2020 NEC: 210.8(B) The correct answer is: I, II & III Type MC cable is available with two grounding conductors. One of these is green and the second one is green with ___ stripes. Select one: w of these - The correct answer is: yellow Ground-fault circuit interrupters are designed to trip at current levels above ___. Select one: a.10 mA b.6 A c.6 mA d.20 A e.4 A - 2020 NEC: 100_Ground-Fault Circuit Interrupter I-Note The correct answer is: 6 mA Although protected with a GFCI breaker, a person could still feel a shock. Select one: a.True b.False - The correct answer is: True Equipment grounding conductors installed in raceways for isolated ground receptacles are required to ___. Select one: continuous, without joints or splices copper insulated green insulation without stripes of these - 2020 NEC: 250.96(B) The correct answer is: be insulated Two 20-amp, 120-volt GFCI breakers are installed in spaces 8 & 10 in a 120/240-volt 1Ø, 3-wire panel. These two circuits will be installed in one conduit. You must install at least ___ neutral(s) in the conduit. Select one: a.1 b.2 c.3 d.0 - The correct answer is: 2 A conduit system of PVC and RMC was installed in the slab between the bottom of the panel and a metal switch box in the wall. A 15-amp branch circuit (including a "hot," a neutral, an EGC, and an isolated grounding conductor) was installed in the PVC/RMC. The receptacle shown here was connected and installed in the metal switch box and a stainless steel cover was installed on the receptacle.Figure 309.71 Refer to Figure 309.71. Using a voltmeter on the energized receptacle, your meter would indicate ___ volts, if the leads were connected between point C and the metal cover. - The correct answer is: 120 A conduit system of PVC and RMC was installed in the slab between the bottom of the panel and a metal switch box in the wall. A 15-amp branch circuit (including a "hot," a neutral, an EGC, and an isolated grounding conductor) was installed in the PVC/RMC. The receptacle shown here was connected and installed in the metal switch box and a stainless steel cover was installed on the receptacle.Figure 309.71 Refer to Figure 309.71. Using a voltmeter on the energized receptacle, your meter would indicate ___ volts if the leads were connected between points A and C. - The correct answer is: 120 Refer to Figure 308.22. Only one EGC will be installed in the EMT between the panel and the metal pull box. Splices will be made at the ground bar in the pull box to drop an EGC to each load. Does the NEC® require the insulated ground bar to be connected to the metal pull box? Select one: a.Yes b.No - 2020 NEC: 250.148(C) The correct answer is: Yes A separate water piping bonding jumper ___ required where the metal frame of a building or structure is used as the grounding electrode for a separately derived system and is bonded to the metal water piping in the area served by the separately derived system. Select one: not be be - 2020 NEC: 250.104(D)(1) Exc 2 The correct answer is: shall not be Where used in a corrosive environment at a wastewater treatment plant, ___ equipment bonding jumpers are permitted.I. aluminum II. copper Select one: a.I only b.II only r I or - 2020 NEC: 250.102(A) The correct answer is: II only For Figure 309.73, a meter would indicate ___ ohms between points B and C. Select one: a.∞ (or OL on a digital meter) b.0 - The correct answer is: 0 For Figure 309.73, a meter would indicate ___ ohms between points A and C. Select one: a.∞ (or OL on a digital meter) b.0 - The correct answer is: ∞ (or OL on a digital meter) Which of these box-receptacle combinations require(s) the installation of a grounding jumper (pigtail) from the receptacle to the box? All boxes and conduits are metal. Separate EGCs were NOT installed with these circuits.I. a receptacle installed on a surface-mounted "bell" box where both washers were removed from the receptacle mounting screwsII. a self-grounding receptacle mounted on a switch box that is set back in the sheetrock wall not more than 1/ 4 inch where the washer was removed from the receptacle mounting screwsIII. a receptacle on a surface-mounted handy box where both washers were removed from the receptacle mounting screws Select one: a.I only b.I, II & III c.I & III only d.II only of these - 2020 NEC: 250.146 The correct answer is: none of these To apply the exception to NEC® 250.140, the existing wiring method to a 120/240-volt range can be ___.I. 8-2 with ground Type NM cableII. 8-3 (without ground) Type NM cableIII. 8-3 Type SE cable (all three conductors insulated) Select one: a.III only b.II or III only c.I or II only d.I, II or III - 2020 NEC: 250.140 Exc The correct answer is: II or III only Section ___ of the NEC® permits the equipment grounding conductor used as an isolated grounding conductor to pass through a metal box without being connected to the box. Select one: a.250.149 b.250.148 c.250.146 d.250.66 - 2020 NEC: 250.146(D) The correct answer is: 250.146 Four metal 4"-Square boxes with 1-gang metal plaster rings are roughed into a wall that will be covered with sheetrock. The plaster rings are 1/2" rise and the sheetrock is 5/8". Self-grounding 120-volt duplex receptacles are to be installed at each box. The home run is stubbed up out of the slab with PVC to hit the first box, and EMT is used to loop the other boxes together. The neutral, EGC, and ungrounded conductors are "pigtailed" in the first three boxes and are connected directly to the receptacle in the last box. Does the NEC® require the ground at the last box to be bonded to this box where the ground WAS bonded to the first box? Select one: a.Yes b.No - 2020 NEC: 250.148 The correct answer is: Yes

Show more Read less
Institution
IEC 3A
Course
IEC 3A











Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
IEC 3A
Course
IEC 3A

Document information

Uploaded on
January 7, 2025
Number of pages
110
Written in
2024/2025
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

IEC 3A TEST BANK QUESTIONS
AND CORRECT ANSWERS
(VERIFIED ANSWERS) ALREADY
PASSED

When an isolated ground receptacle is installed in a metal box, a(n) ___ equipment
grounding conductor is required for connection to the metal box.
Select one:
a.separate
b.bare copper
c.oversized
d.insulated - 2020 NEC: 250.96(B)
The correct answer is: separate

The equipment grounding conductor is permitted to be run separately from the circuit
conductors when ___.
Select one:
a.installed in industrial establishments only
b.the equipment grounding conductor has the same insulation as the circuit conductors
c.a nongrounded-type receptacle is replaced
d.the branch circuit is less than 30 amperes - 2020 NEC: 250.130(C)
The correct answer is: a nongrounded-type receptacle is replaced

Which of the following receptacles are required to be GFCI protected? I. where installed
in a patient's room in a hospital II. where installed on the exterior wall (outdoors) of an
elementary schoolIII. where installed adjacent to (2 feet away from) a sink in a bar -
2020 NEC: 210.8(B)(4) | 2020 NEC: 210.8(B)(5)
The correct answer is: II & III only

Which of the following receptacles are required to be GFCI protected?I. where installed
outside on the exterior wall of a restaurantII. where installed on the wall at 18" AFF
(NOT above a countertop) in the kitchen at a restaurantIII. where installed on the
exterior wall (outdoors) of an elementary school
Select one:
a.II only
b.I, II & III
c.I only
d.II & III only
e.III only - 2020 NEC: 210.8(B)

,The correct answer is: I, II & III

Type MC cable is available with two grounding conductors. One of these is green and
the second one is green with ___ stripes.
Select one:
a.white
b.red
c.yellow
d.none of these - The correct answer is: yellow

Ground-fault circuit interrupters are designed to trip at current levels above ___.
Select one:
a.10 mA
b.6 A
c.6 mA
d.20 A
e.4 A - 2020 NEC: 100_Ground-Fault Circuit Interrupter I-Note
The correct answer is: 6 mA

Although protected with a GFCI breaker, a person could still feel a shock.
Select one:
a.True
b.False - The correct answer is: True

Equipment grounding conductors installed in raceways for isolated ground receptacles
are required to ___.
Select one:
a.be continuous, without joints or splices
b.be copper
c.be insulated
d.have green insulation without stripes
e.all of these - 2020 NEC: 250.96(B)
The correct answer is: be insulated

Two 20-amp, 120-volt GFCI breakers are installed in spaces 8 & 10 in a 120/240-volt
1Ø, 3-wire panel. These two circuits will be installed in one conduit. You must install at
least ___ neutral(s) in the conduit.
Select one:
a.1
b.2
c.3
d.0 - The correct answer is: 2

A conduit system of PVC and RMC was installed in the slab between the bottom of the
panel and a metal switch box in the wall. A 15-amp branch circuit (including a "hot," a
neutral, an EGC, and an isolated grounding conductor) was installed in the PVC/RMC.

,The receptacle shown here was connected and installed in the metal switch box and a
stainless steel cover was installed on the receptacle.Figure 309.71
Refer to Figure 309.71. Using a voltmeter on the energized receptacle, your meter
would indicate ___ volts, if the leads were connected between point C and the metal
cover. - The correct answer is: 120

A conduit system of PVC and RMC was installed in the slab between the bottom of the
panel and a metal switch box in the wall. A 15-amp branch circuit (including a "hot," a
neutral, an EGC, and an isolated grounding conductor) was installed in the PVC/RMC.
The receptacle shown here was connected and installed in the metal switch box and a
stainless steel cover was installed on the receptacle.Figure 309.71
Refer to Figure 309.71. Using a voltmeter on the energized receptacle, your meter
would indicate ___ volts if the leads were connected between points A and C. - The
correct answer is: 120

Refer to Figure 308.22. Only one EGC will be installed in the EMT between the panel
and the metal pull box. Splices will be made at the ground bar in the pull box to drop an
EGC to each load. Does the NEC® require the insulated ground bar to be connected to
the metal pull box?
Select one:
a.Yes
b.No - 2020 NEC: 250.148(C)
The correct answer is: Yes

A separate water piping bonding jumper ___ required where the metal frame of a
building or structure is used as the grounding electrode for a separately derived system
and is bonded to the metal water piping in the area served by the separately derived
system.
Select one:
a.shall not be
b.shall be - 2020 NEC: 250.104(D)(1) Exc 2
The correct answer is: shall not be

Where used in a corrosive environment at a wastewater treatment plant, ___ equipment
bonding jumpers are permitted.I. aluminum II. copper
Select one:
a.I only
b.II only
c.either I or - 2020 NEC: 250.102(A)
The correct answer is: II only

For Figure 309.73, a meter would indicate ___ ohms between points B and C.

Select one:
a.∞ (or OL on a digital meter)
b.0 - The correct answer is: 0

, For Figure 309.73, a meter would indicate ___ ohms between points A and C.

Select one:
a.∞ (or OL on a digital meter)
b.0 - The correct answer is: ∞ (or OL on a digital meter)

Which of these box-receptacle combinations require(s) the installation of a grounding
jumper (pigtail) from the receptacle to the box? All boxes and conduits are metal.
Separate EGCs were NOT installed with these circuits.I. a receptacle installed on a
surface-mounted "bell" box where both washers were removed from the receptacle
mounting screwsII. a self-grounding receptacle mounted on a switch box that is set back
in the sheetrock wall not more than 1/ 4 inch where the washer was removed from the
receptacle mounting screwsIII. a receptacle on a surface-mounted handy box where
both washers were removed from the receptacle mounting screws
Select one:
a.I only
b.I, II & III
c.I & III only
d.II only
e.none of these - 2020 NEC: 250.146
The correct answer is: none of these

To apply the exception to NEC® 250.140, the existing wiring method to a 120/240-volt
range can be ___.I. 8-2 with ground Type NM cableII. 8-3 (without ground) Type NM
cableIII. 8-3 Type SE cable (all three conductors insulated)
Select one:
a.III only
b.II or III only
c.I or II only
d.I, II or III - 2020 NEC: 250.140 Exc
The correct answer is: II or III only

Section ___ of the NEC® permits the equipment grounding conductor used as an
isolated grounding conductor to pass through a metal box without being connected to
the box.
Select one:
a.250.149
b.250.148
c.250.146
d.250.66 - 2020 NEC: 250.146(D)
The correct answer is: 250.146

Four metal 4"-Square boxes with 1-gang metal plaster rings are roughed into a wall that
will be covered with sheetrock. The plaster rings are 1/2" rise and the sheetrock is 5/8".
Self-grounding 120-volt duplex receptacles are to be installed at each box. The home

Get to know the seller

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
Scholarsstudyguide nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
787
Member since
3 year
Number of followers
475
Documents
15377
Last sold
1 day ago
NURSING

Here you will find everything you need in nursing Assignments, EXAMS AND TESTBANKS. For students who want to see results twice as fast. I strive for my content to be of the highest quality. Always leave a review after purchasing any document so as to make sure our customers are 100% satisfied.

3.9

164 reviews

5
87
4
21
3
26
2
6
1
24

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions