Inspection, testing, servicing, and other maintenance of sprinkler systems must be - ANSWERSpersonally supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011 edition.
Automatic and non-automatic sprinkler systems shall be inspected, tested and maintai...
Inspection, testing, servicing, and other maintenance of sprinkler systems must be - ANSWERSpersonally
supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011
edition.
Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required by
NFPA #25 2011 edition by - ANSWERScompetent person holding a S-12 Certificate of Fitness and
employed or contracted by the owner
How long must maintenance records be kept? - ANSWERSMinimum 3 years
If there are 300 sprinkler heads or less how many spares must be kept on premises - ANSWERSAt least 6
How often do sprinkler connections need a hydrostatic pressure test? - ANSWERS5 years
Who maintains the records of inspections, tests, servicing, and other items of maintenance? -
ANSWERSImpairment coordinator
Who assigns the impairment coordinator - ANSWERSBuilding owner
Under what conditions should the fire department be notified regarding a system that is out of service? -
ANSWERS- out of service on more than 1 floor of a building or
- the repair cannot be completed in less than 8 hours or
-there are one or more fire protection services out of order at the same time
When the Cof holder observes a minor defect, he shall report the condition to the ____ ____ and if it is
not corrected within ____ days it shall be deemed an ____ and reported in _____ to the ____ ____. -
ANSWERSBuilding owner, 30, impairment, writing, FD
,Systems that are out of service, both planned and unplanned shall be identified by placing a tag on the
following locations: - ANSWERS- FD connections
- system control valves
- fire command center
- or clear visible location in lobby ofbuilding
Who is required to post tags at the main control valve? - ANSWERS- master fire suppression contractor
(class a or b)
-master plumber
Where would a green tag be placed? - ANSWERSMain control valve
If a system is fully out of service, what color and where should tags be placed? - ANSWERS- white disc on
all affected fire department connections
- red disc on main control valve
If a system is particularly out of service, what color and where should tags be placed? - ANSWERS-Blue
disc on all affected fire department connections
- red disc on main control valve
What should the red tag on the main control valve include? - ANSWERS- sprinkler company name
- date of removal from service
- anticipated working date
What should the tags indicate? - ANSWERS- area affected
- brief description of condition
-occupancy classification
- COF #
- est. time system will be operational
, What color are tags if no impairment is found? - ANSWERSGreen
Who are the ONLY people permitted to place a tag on a underground service main, water storage tank,
control valve, fire department connection, or booster pumps? - ANSWERSFDNY, owner, MFSPC or Master
plumber
Approved nonfreezing solutions include glycerin not greater than---- and glycon greater than ---- non
freezing solution - ANSWERS48%/38%
What is a riser card - ANSWERSAn approved card baring the dates of inspection, COF #, and signature of
COF holder.
Where should the riser card be placed? - ANSWERSOh the premesis near the main water supply control
valve
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________
SPRINKLER HEADS OR LESS. - ANSWERS30
Alarm Notification Appliance - ANSWERSA fire alarm system component, such as a bell, horn, speaker,
light, text display or vibration device that issues an audible, tactile, and/or visual alert
Alarm signal - ANSWERSA signal indicating an emergency requiring immediate action, such as a signal
indicative of fire.
Antifreeze Sprinkler System - ANSWERSA wet pipe sprinkler system employing automatic sprinklers that
are attached to a piping system that contains an antifreeze solution and is connected to a water supply.
The antifreeze solution is discharged, followed by water, immediately upon operation of sprinklers
opened by heat from a fire.
AUTOMATIC BALL DRIP DEVICES SHALL BE INSTALLED IN THE _________ POSITION. - ANSWERShorizontal
Los beneficios de comprar resúmenes en Stuvia estan en línea:
Garantiza la calidad de los comentarios
Compradores de Stuvia evaluaron más de 700.000 resúmenes. Así estas seguro que compras los mejores documentos!
Compra fácil y rápido
Puedes pagar rápidamente y en una vez con iDeal, tarjeta de crédito o con tu crédito de Stuvia. Sin tener que hacerte miembro.
Enfócate en lo más importante
Tus compañeros escriben los resúmenes. Por eso tienes la seguridad que tienes un resumen actual y confiable.
Así llegas a la conclusión rapidamente!
Preguntas frecuentes
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
100% de satisfacción garantizada: ¿Cómo funciona?
Nuestra garantía de satisfacción le asegura que siempre encontrará un documento de estudio a tu medida. Tu rellenas un formulario y nuestro equipo de atención al cliente se encarga del resto.
Who am I buying this summary from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller papersmaster01. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy this summary for $14.99. You're not tied to anything after your purchase.