Which of the following is not one of the three primary fire protection elements for
providing fire protection in a building? - answer Reporting

Which of the following are considered as primary functions of a fire alarm system? -
answer Actuation of emergency control functions, building system management, early
detection of fires, notifications of the fire department, occupant notification.

The world's first public fire alarm reporting system was used in? - answer Boston

Fusible link technology was first used for? - answer Heat detectors

The first ? was made commercially available in the 1960s. - answer Smoke-detector

Single-station smoke alarms for dwellings are only used for ? - answer Life safety

Air-sampling smoke detectors were developed in? - answer Australia

What type of detection was developed to protect large open areas? - answerProjected
beam smoke detectors

The Americans with Disabilities Act (ADA) became law in the? - answer1990s

Central, Proprietary, and Remote are all examples of ? systems. - answerSupervising
system

Supervising stations that only monitor property owned by the supervising station
operator are called? - answerProprietary supervising stations

An in-building fire emergency voice/alarm communications system is usually found in
a ? - answerHigh-rise building

The primary purpose of dwelling fire warning equipment or systems is ? - answerLife
Safety

A ? usually provides signal information in a floor plan format - answerGraphic
annunciator

A fire alarm control unit performs which of the following functions? - answerProvides
graphical user interface, monitoring of circuits, power to initiating devices

,An addressable fire alarm system control unit monitors the status of initiating devices ? -
answerby periodically polling the device

Which type of sprinkler is most commonly used to protect buildings? - answerWet-pipe
sprinklers

Which of the following is an alarm signal initiating device? - answerManual station

Which of the following is considered an emergency safety control function? -
answerDoor unlocking, elevator recall, elevator shutdown

A ? system usually requires the actuation of ? detector(s) to open the charging valve,
which floods the sprinkler piping in the protected space. - answerPre-action / 2

Which of the following types of notification appliances are frequently used to alert
occupants? - answerHorns, speakers, strobes

? is an example of an emergency control function that may be controlled by a fire alarm
system. - answerElevator recall or shutdown

supervisory initiating device - answerValve tamper switch

Which of the following circuit types is addressable? - answerSLC

Computer rooms are sometimes protected by ? - answergaseous suppression systems

The National Fire Protection Association was founded in ? - answer1896

Which of the following features resulted from large-loss fires? - answerAutomatic
sprinklers, door unlocking, panic hardware

The safety system in the U.S. is comprised of which of the following? - answerProducts
standards, codes, standards, and enforcement

Codes usually contain ? -based requirements, while standards usually contain ?
requirements. - answerOccupancy / Installation

Which of the following is considered an authority having jurisdiction for fire alarm
systems? - answerElectrical inspector, fire marshal, insurance interest

Annex A of NFPA 72 is enforceable as Code and is mandatory. - answerFalse

Alarm-Initiating Devices - answerHeat detectors, smoke detectors, manual fire alarm
boxes, radiant energy fire detectors, pressure-type sensing switches, and paddle-type
water flow switches

, Which of the following types of circuits will require an EOL? - answerIDC

Circuit description to its type - answerAddressable Type Circuit -SLC, Conventional
Zone Type Circuit - IDC, Output Circuit - NAC

Trouble - answerIndicates a fault on wiring, power supply of communications

Alarm - answerIndicates a life threatening (emergency) condition

Indicate an impaired or off-normal suppression system? - answerSupervisory

May indicate actuation of a duct smoke detector? - answerSupervisory

Fire alarm systems produce which of the following signals? - answerAlarm, supervisory,
trouble

Opens and grounds on a fire alarm circuit will result in a(n) ? signal - answerTrouble

Alarm signals are indicative of a ? - answerfire or other life-threatening emergency

A valve tamper switch, when actuated, will produce a(n) ? signal. - answerSupervisory

Duct smoke detectors are sometimes permitted to cause a(n) ? signal in place of a
supervisory signal. - answerAlarm

An emergency communications system (ECS) can be used to warn occupants of a ? . -
answerFire, terrorist attack, tornado

Section ? of NFPA 72 requires all circuits to be monitored for integrity. - answer12.6

Wiring between enclosures is not required to be monitored for integrity if the enclosures
are less than ? apart and the wiring is ? . - answer20' / installed in conduit

Which of the following are types of fire alarm circuits? - answerNAC,IDC,SLC

Initiating device circuits and notification appliance circuits monitor for integrity by ? . -
answerA small current through the circuit

Which of the following conditions can result in a failure to monitor devices and circuits
for integrity? - answerT-Tapping

Signaling line circuits monitor for integrity by ? . - answerInterrogating field devices

Notification appliances commonly use a(n) ? to prevent monitoring current to pass
through the notification appliance circuitry. - answerBlocking diode

Voordelen van het kopen van samenvattingen bij Stuvia op een rij:

Verzekerd van kwaliteit door reviews

Verzekerd van kwaliteit door reviews

Stuvia-klanten hebben meer dan 700.000 samenvattingen beoordeeld. Zo weet je zeker dat je de beste documenten koopt!

Snel en makkelijk kopen

Snel en makkelijk kopen

Je betaalt supersnel en eenmalig met iDeal, creditcard of Stuvia-tegoed voor de samenvatting. Zonder lidmaatschap.

Focus op de essentie

Focus op de essentie

Samenvattingen worden geschreven voor en door anderen. Daarom zijn de samenvattingen altijd betrouwbaar en actueel. Zo kom je snel tot de kern!

Veelgestelde vragen

Wat krijg ik als ik dit document koop?

Je krijgt een PDF, die direct beschikbaar is na je aankoop. Het gekochte document is altijd, overal en oneindig toegankelijk via je profiel.

Tevredenheidsgarantie: hoe werkt dat?

Onze tevredenheidsgarantie zorgt ervoor dat je altijd een studiedocument vindt dat goed bij je past. Je vult een formulier in en onze klantenservice regelt de rest.

Van wie koop ik deze samenvatting?

Stuvia is een marktplaats, je koop dit document dus niet van ons, maar van verkoper julianah420. Stuvia faciliteert de betaling aan de verkoper.

Zit ik meteen vast aan een abonnement?

Nee, je koopt alleen deze samenvatting voor €15,31. Je zit daarna nergens aan vast.

Is Stuvia te vertrouwen?

4,6 sterren op Google & Trustpilot (+1000 reviews)

Afgelopen 30 dagen zijn er 72042 samenvattingen verkocht

Opgericht in 2010, al 14 jaar dé plek om samenvattingen te kopen

Start met verkopen
€15,31
  • (0)
  Kopen