QUESTIONS AND ANSWERS
Pumps6rated6at6less6than630006gpm6-6ans--100%6capacity6at61506psi
Pumps6rated6at6less6than615006gpm6shall6be6capable6of6taking6suction6through6__6of6suc
tion6hose6in6not6more6than6306seconds6-6ans--20'
Pumping6system6shall6develop6__6inHg6of6vacuum6by6primer6pump6and6sustaining6the6v
acuum6for656min6with6a6loss6not6too6exceed6106in.Hg6-6ans--22
The6pump6body6shall6be6subjected6to6a6hydrostatic6test6to6a6gauge6pressure6of6____6for6
106min6-6ans--5006psi
Discharge6piping6system6hydrodynamic6discharge6pressure6of6___6or6___6over6maximu
m6discharge6pressure6capability6of6pump,6whichever6is6greater6-6ans--500/100
Aerial6waterway6and6master6stream6waterway6hydrostatic6test6pressure6-6ans--2506psi
All6testing6shall6be6witnessed6by6-6ans--In6person6independent6third6party
Fire6pump6rated6less6than67506gpm6shall6be6subjected6to6a6____6min6pumping6from6draft
6-6ans--50
Water6depth6for6pump6test6-6ans--4'
Water6temp6for6pump6test6-6ans--35-1106degrees
Minimum6lift6from6center6of6pump6intake6to6surface6of6water6-6ans--3'
All6gauges6shall6be6calibrated6in6the6_____6proceeding6the6test6-6ans--Month
Master6gauge6meeting6the6requirements6for6grade63A6or64A6shall6be6calibrated6within6th
e6preceding6-6ans--Year
Engine6tach6shall6be6accurate6within6-6ans--+-506rpm
Pumps6rated6at67506to630006gpm6test6time6-6ans--36hours