100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
IEC 213 QUESTIONS WITH SOLUTIONS 2024 CA$21.65   Add to cart

Exam (elaborations)

IEC 213 QUESTIONS WITH SOLUTIONS 2024

 19 views  0 purchase
  • Course
  • IEC
  • Institution
  • IEC

Exam of 5 pages for the course IEC at IEC (IEC 213)

Preview 2 out of 5  pages

  • October 16, 2024
  • 5
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • IEC
  • IEC
avatar-seller
IEC 213

When the corrected ampacity of a 10 AWG copper conductor is 12.86 amps, the
maximum size circuit breaker permitted to protect the conductors is ___. - answer15

According to 240.4(D)(7), the largest circuit breaker that can be used to protect a circuit
that uses 10 AWG conductors has a rating of ___ A. - answer30

A 240-volt load, such as a window unit air conditioner, would require breaker ___ to be
installed in the panelboard. - answerb

Generally, circuit breakers must be ___. - answer readily accessible

What is the maximum voltage between circuit conductors when using plug fuses? -
answer125

Refer to Figure 204.5. The conductors at Point I are ___. - answertaps

Where installed in a 3-pole, 600-volt fused safety switch, the minimum number of fuses
required to protect a 120-volt, 1-ph, 2-wire branch circuit is ___. - answer1

The secondary of a 300 KVA, 480 - 240-volt Δ-Δ transformer is delivering 100 amps to
3Ø loads. Based on this load, the smallest permitted primary and secondary conductors
are installed.

Refer to Scenario 223.51. The maximum rating of the primary OCPD is ___ A. -
answer100

The secondary of a 300 KVA transformer delivers power to a 180-amp, 3Ø load. This is
a 480 — 240 volt Δ-Δ transformer. Primary and secondary conductors are the minimum
size required to serve the load.

Refer to Scenario 220.53. The secondary OCPD can have a rating no greater than ___
amps. - answer200

Section 240.21(C)(6) in the NEC® is the "25 foot rule." This section requires that the
secondary conductors be 25 feet or shorter in length and ___.

I. have an ampacity that is ≥ [(Pri OCPD ÷ 3) × (Epri line ÷ Esec line)]
II. have an ampacity that is ≥ the rating of the circuit breaker or fuses at the end
III. be installed in a raceway or otherwise protected from physical damage - answerI, II,
& III

, Circuit breakers shall be marked with a voltage rating not less than the nominal system
voltage that is indicative of their capability to interrupt fault currents ___.
I. between phases
II. from phase to ground
III. between the neutral and ground - answerI & II only

Handles or levers of circuit breakers, and similar parts which may move suddenly in
such a way that persons in the vicinity are likely to be injured by being struck by them,
shall be ___.
I. concealed
II. isolated
III. guarded - answerII or III only

If a fuse label is not marked with a fuse interrupting rating, the fuse size has ___. -
answeran interrupting rating of 10,000 amps

A conductor has a computed ampacity of 75 amps. What is the maximum standard
ampere rating of the overcurrent protection device the NEC® permits to protect this
circuit? This is not a motor circuit or part of a multioutlet branch circuit supplying
receptacles. - answer80 amperes

If the allowable current rating of a busway is 1400 amps, what is the maximum
allowable rating of the overcurrent protection device that may be used to protect the
busway? - answer1200 amps

The use of the term SPD is becoming quite common and is addressed in NEC® Article
___. - answer242

Unless specifically listed for them, a surge-protected device is not permitted on a(n) ___
system. - answerimpedance-grounded

If installed, a surge protective device shall be connected to each ___ conductor. -
answerungrounded

When ___ touch together, this is a ground fault.
I. two ungrounded circuit conductors
II. an ungrounded and a grounded circuit conductor
III. an ungrounded circuit conductor and the metal conduit - answerIII only

One conduit is run from Panel LA to a pull box as shown in Figure 205.13. The 250-amp
breaker has 250 kcmil circuit conductors connected to it, and 500 kcmil circuit
conductors are connected to the 400-amp breaker. Only one grounding conductor is
required in this conduit for all contained circuits. The smallest EGC permitted to be
installed in the conduit between the panel and the pull box is ___ AWG.

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller julianah420. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for CA$21.65. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

75323 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
CA$21.65
  • (0)
  Add to cart