Qualification for S98 certificate of fitness include all except - ANSWERSMust be 21 years of age
If you fail the written test you will not be permitted to Retest for - ANSWERS90 days
The following is an example of what type of Ceiling - ANSWERSStooped
A bean is defined as a structural or n...
FSDNY S98 Questions & Answers 100%
Correct!
Qualification for S98 certificate of fitness include all except - ANSWERSMust be 21
years of age
If you fail the written test you will not be permitted to Retest for - ANSWERS90 days
The following is an example of what type of Ceiling - ANSWERSStooped
A bean is defined as a structural or non structural solid member which could jacks down
into the rooms base more than _____ and is located more than _____ apart on center -
ANSWERSDown more than4" and 3' apart
The following are examples of line type detection except - ANSWERSionization smoke
detector
He could tonight a circuit to which automatic or manual initiating devices are connected
where the signal received does not identify the device operated is called? -
ANSWERSA signaling line circuit
Secondary power supplies are required to have sufficient power to operate the fire
alarm system in a non alarm condition for _______ hours and then be capable of
operating all notification devices for a minimum of ______ minutes - ANSWERS24
hours and 5 minutes
Secondary power supplies for emergency voice evacuation systems are required to
have sufficient power to operate the system in a non along condition for ______ hours
and kin be capable of operating the system during a fire or other emergency for a
minimum of ______ minutes - ANSWERS24 hours and 15 minutes under maximum
load
Secondary power supply shall automatically provide power to the protected premises
fire alarm system within _______ seconds when ever primary power fails to provide
minimum voltage required for proper operation? - ANSWERS10 seconds
Cording to NFPA chapter 4, batteries shall be permanently marked with what
information? - ANSWERSMonth and year of manufacture
NFPA 72 "record of completion" is prepared: - ANSWERSupon completion of
installation at just acceptance test
, According to NFPA chapter 4, the control panel charging apparatus shall be taken full of
recharging batteries within _____ _____ after batteries have been fully discharged? -
ANSWERS24 hours
According to the fire code of New York City, smoke detectors may be tested by the
following methods except for: - ANSWERSMeasured aerosol smoke introduced into the
detector
What type of drawing typically shows correct conductor counts? - ANSWERSRiser
diagrams
According to the fire code and fire rules, who is responsible for preventing unnecessary
and unwanted alarms? - ANSWERSOwner of a promise or a part thereof
I'll take you way and which according to NFPA chapter 4, a coded alarm signal shall
consist of not less than ______ complete rounds of the number transmitted. Each round
shall consist of not less than a ______ impulses - ANSWERS3 rounds and 3 impulses
According to the fire rules, who is responsible for making in trees in the smoke detector
maintenance log? - ANSWERSThe fire safety director or a person designated by
building owners if no FSD
According to NFPA chapter 4, installation Conductors shall be monitored for integrity.
The occurrence of a single open or single ground fault condition shall be automatically
indicated within ______ seconds - ANSWERS200 seconds
All of the following are good conductors of electricity except - ANSWERScarbon
Which of the following is an example of an initiating device? - ANSWERSSupervisory air
pressure switch and photo electric smoke detector
Into voice along and initiating device which is destroyed as a result of its operation is
what type? - ANSWERSNon restorable
It's the face of the nobleman equipment you shall be designed so that it is capable of
performing its intended function at ______ of its name plate voltage - ANSWERS85%
When installing heat detectors on ceilings, a row detector shall be located -
ANSWERSWithin 3' of the peak
The minimum distance for mounting of a spot type smoke detector from an air supply
diffuser is? - ANSWERS3' from diffusers
This is regarding manual fire alarm boxes, NFPA 72 requires that they be conspicuous,
unobstructed, and ________ - ANSWERSaccessible
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller papersmaster01. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for £10.60. You're not tied to anything after your purchase.