Per NFPA 20 requirements, which of the following is required to
illuminate a pump room or pump house. Correct Answer-Artificial Light
Before shipment from the factory, each pump shall be hydrostatically
tested by the manufacturer. The test pressure shall not be less than one-
half times the sum of the pump's shutoff heads plus its maximum
allowable suction head, but shall not be less than, Correct Answer-200
PSI
The weekly test for an electric pump requires the pump to run for a
minimum of Correct Answer-10 Minutes
The distance between the bottom of strainer and the bottom of the wet
pit on a vertical shaft turbine pump should be: Correct Answer-One half
of the pump diameter but not less than 12 inches
Engine generator sets supplying emergency or standby power to fire
pump assemblies shall be periodically tested in accordance with which
of the following NFPA standards: Correct Answer-NFPA 110
A pump for fire protection shall be selected to operate at less than or
equal to _% of the rated capacity. Correct Answer-150
, A fire pump controller shall be permitted to be used as a junction box to
supply other equipment. Correct Answer-False
Authority Having Jurisdiction (AHJ) is the organization, office, or
individual responsible for approving equipment, materials, installations
or procedures. Correct Answer-True
Which of the following conditions requires the installation of a listed
indicating butterfly or gate valve and a drain valve or ball drip located in
the pipeline to the hose valve header: Correct Answer-Both A and B
The maximum allowable shutoff head for a pump with a rated capacity
of 900 gpm and a rated head of 250 feet is: Correct Answer-350 Feet
Maximum number of drivers permitted to equip a fire pump is Correct
Answer-One
Which of the following valves allows the diversion of liquid to limit
excess pressure in a system: Correct Answer-A relief valve
The fire pump, driver, controller, water supply and power supply are
required to be protected against possible interruption of service from
damage caused by which of the following: Correct Answer-All of the
above
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller cracker. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for £11.01. You're not tied to anything after your purchase.