DURING AN ANNUAL INSPECTION YOU NOTICE THAT A PENDANT SPRINKLER HEAD HAS BEEN INSTALLED IN THE UPRIGHT POSITION. WHAT ACTION MUST BE TAKEN? correct answers REPLACE THE SPRINKLER WITH AN UPRIGHT SPRINKLER. NFPA 25 5.2.1.1
WHICH OF THE FOLLOWING CONDITIONS DOES NOT REQUIRE SPRINKLER REPLACEMENT? L...
during an annual inspection you notice that a pend
Written for
NFPA 25 |
NFPA 25 |
Seller
Follow
FullyFocus
Reviews received
Content preview
NFPA 25 || with A+ Guaranteed Solutions.
DURING AN ANNUAL INSPECTION YOU NOTICE THAT A PENDANT SPRINKLER
HEAD HAS BEEN INSTALLED IN THE UPRIGHT POSITION. WHAT ACTION MUST BE
TAKEN? correct answers REPLACE THE SPRINKLER WITH AN UPRIGHT SPRINKLER.
NFPA 25 5.2.1.1
WHICH OF THE FOLLOWING CONDITIONS DOES NOT REQUIRE SPRINKLER
REPLACEMENT? LOADING. LOSS OF FLUID IN GLASS BULB. MATRICULATION.
ALL OF THESE CONDITIONS REQUIRE REPLACEMENT. correct answers ANSWER.
MATRICULATION. NFPA 25 5.2.1.1.2
WHICH OF THE FOLLOWING IS NOT REQUIRED TO BE INSPECTED ANNUALLY?
CORRECT NUMBER OF SPARE SPRINKLERS. SPRINKLER WRENCH. SPRINKLER
PIPING. SPRINKLER SYSTEM GAUGES. correct answers ANSWER. SPRINKLER
SYSTEM GAUGES. NFPA 25 TABLE 5.1.1.2
WATER FLOW ALARM DEVICES SHALL BE INSPECTED correct answers QUARTERLY.
NFPA 25 TABLE 5.1.1.2
WHAT IS THE INSPECTION FREQUENCY FOR THE HYDRAULIC DESIGN
INFORMATION SIGN? correct answers QUARTERLY. NFPA 25 TABLE 5.1.1.2
WHICH OF THE FOLLOWING FIRE PUMP INSPECTIONS IS NOT WEEKLY? DIESEL
ENGINE CRANKCASE BREATHER. SUCTION RESERVOIR IS FULL. FUEL TANK IS 2/3
TWO THIRDS FULL. PUMP SYSTEM PIPING IS FREE OF LEAKS. correct answers
ANSWER. DIESEL ENGINE CRANKCASE BREATHER. NFPA 25 TABLE 8.1.2
WHAT IS THE INSPECTION FREQUENCY FOR A DIESEL FUEL FIRE PUMP OIL
LEVEL? correct answers WEEKLY. NFPA 25 TABLE 8.1.2
CONSIDER A HORIZONTAL FIRE PUMP. WHICH OF THE FOLLOWING IS NOT A
REQUIRED OBSERVATION BEFORE PUMPING? CHECK DRIP POCKETS UNDER
PACKING GLANDS FOR PROPER DRAINAGE. CHECK PACKING ADJUSTMENT,
APPROXIMATELY ONE DROP PER SECOND IS NECESSARY TO KEEP PACKING
LUBRICATED. OBSERVE SUCTION AND DISCHARGE GAUGES. OBSERVE PACKING
GLANDS FOR PROPER LEAKAGE FOR COOLING OF PACKING. correct answers
OBSERVE PACKING GLANDS FOR PROPER LEAKAGE FOR COOLING OF PACKING.
NFPA 25 A8.2.2
CONSIDER AN ELECTRICAL SYSTEM FOR A FIRE PUMP. WHAT IS THE INSPECTION
FREQUENCY FOR THE EMERGENCY MANUAL STARTING MEANS? correct answers
ANNUALLY. NFPA 25 8.1.2
ANY ABNORMALITY OBSERVED DURING INSPECTION SHALL BE REPORTED
PROMPTLY TO? correct answers PROPERTY OWNER. NFPA 25 8.4.1
,WHAT IS THE INSPECTION FREQUENCY FOR THE INTERIOR OF A WATER
STORAGE TANK WITHOUT CORROSION, OR WITHOUT CORROSION PROTECTION?
correct answers 3 YEARS. NFPA 25 TABLE 9.1.1.2
CONSIDER A WATER STORAGE TANK WITH A LOW TEMPERATURE ALARM
CONNECTED TO A CONSTANTLY ATTENDED LOCATION. WHAT IS THE
INSPECTION FREQUENCY FOR THE WATER TEMPERATURE? correct answers
MONTHLY. NFPA 25 TABLE 9.1.1.2
AUTOMATIC TANK FILL VALVES SHALL BE INSPECTED WITH WHAT
FREQUENCY? correct answers WEEKLY. NFPA STATES TESTING OCCURS ANNUALLY
NOT INSPECTION PER QUESTION. NFPA 25 9.5.1.1
THE HOOPS AND GRILLAGE OF WOODEN TANKS SHALL BE INSPECTED WITH
WHAT FREQUENCY? correct answers ANNUALLY. NFPA 25 9.2.5.4
WHAT NFPA STANDARD GOVERNS THE INSTALLATION OF LIGHTNING
PROTECTION SYSTEMS? correct answers NFPA 780 STANDARD FOR THE
INSTALLATION OF LIGHTNING PROTECTION SYSTEMS. NFPA 25 A9.2.5.1
WHAT IS THE INSPECTION FREQUENCY FOR STANDPIPE AND HOSE SYSTEM
PIPING? correct answers ANNUALLY. NFPA 25 6.1.1.2
GAUGES ON AUTOMATIC STANDPIPE SYSTEMS SHALL BE INSPECTED WITH
WHAT FREQUENCY? correct answers QUARTERLY. NFPA 25 6.2.2.1
STANDPIPE AND HOSE SYSTEM SEALED CONTROL VALVES SHALL BE INSPECTED
WITH WHAT FREQUENCY? correct answers WEEKLY. NFPA 25 TABLE 13.1.1.2
STANDPIPE AND HOSE SYSTEM HOSE CONNECTIONS SHALL BE INSPECTED WITH
WHAT FREQUENCY? correct answers ANNUALLY. NFPA 25 13.1.1.2
CONSIDER A STANDPIPE AND HOSE SYSTEM WITH A HYDRAULIC DESIGN
INFORMATION SIGN. WHEN INSPECTING THE INFORMATION SIGN, WHERE
SHOULD IT BE LOCATED FOR AUTOMATIC AND SEMI AUTOMATIC SYSTEMS?
correct answers SECURED TO THE WATER SUPPLY CONTROL VALVE. NFPA 25 A6.2.3
DRY BARREL AND WALL HYDRANTS SHALL BE INSPECTED "BLANK" AND AFTER
EACH OPERATION? correct answers ANNUALLY. NFPA 25 7.2.2.4
AN INSPECTION OF A HYDRANT HOUSE REVEALS THAT IT IS INACCESSIBLE.
WHAT TYPE OF DEFICIENCY IS THIS? correct answers IMPAIRMENT. NFPA 25 TABLE
A.3.3.7
, DEFICIENCY TYPES WHETHER IMPAIRMENT, CRITICAL DEFICIENCY OR NON
CRITICAL DEFICIENCY FOR ALL WATER DELIVERY TYPES ARE LOCATE IN WHICH
TABLE? correct answers TABLE A.3.3.7
MONITOR NOZZLES SHALL BE INSPECTED WITH WHAT FREQUENCY? correct
answers SEMIANNUALLY. NFPA 25 7.2.2.6
MAINLINE STRAINERS SHALL BE INSPECTED AND CLEANED AFTER EACH
SYSTEM FLOW EXCEEDING THAT OF A NOMINAL "BLANK" INCH ORIFICE? correct
answers 2" INCH. NFPA 25 7.2.2.3
HOSE HOUSES SHALL BE INSPECTED WITH WHAT FREQUENCY? correct answers
QUARTERLY. NFPA 25 7.2.2.7
WHAT TYPE OF PIPE IS NOT REQUIRED TO BE INTERNALLY INSPECTED? correct
answers NON-METALLIC. NFPA 25 14.2.1.5
AN INSPECTION OF PIPING AND BRANCH LINE CONDITIONS SHALL BE
CONDUCTED EVERY "BLANK" YEARS BY OPENING A FLUSHING CONNECTION AT
THE END OF ONE MAIN AND BY REMOVING A SPRINKLER TOWARD THE END OF
ONE BRANCH LINE FOR THE PURPOSE OF INSPECTING FOR THE PRESENCE OF
FOREIGN ORGANIC AND INORGANIC MATERIAL? correct answers 5 YEARS. NFPA 25
14.2.1.1
WHAT IS THE PRIMARY PURPOSE OF AN INTERNAL INSPECTION OF PIPE? correct
answers DETERMINE CORROSION. NFPA 25 A.14.2.1.2 AND NFPA 25 A14.3.1
CONSIDER A DRY PIPE SYSTEM WITHOUT AN INSPECTORS TEST VALVE. FOR AN
INTERNAL INSPECTION OF PIPE, WHICH SPRINKLER SHALL BE REMOVED? correct
answers THE SPRINKLER MOST REMOTE FROM THE WATER SOURCE. NFPA 25
A14.2.1
IN LARGE WAREHOUSES, HIGH RISE BUILDINGS AND OTHER BUILDINGS HAVING
MULTIPLE SYSTEMS, IT IS REASONABLE TO PERFORM THE INTERNAL
INSPECTION ON "BLANK" % PERCENT OF THE SYSTEMS IN THE BUILDING? correct
answers 50 PERCENT. NFPA 25 14.2.2
CHECK VALVES SHALL BE INTERNALLY INSPECTED EVERY "BLANK" YEARS
correct answers 5 YEARS. NFPA 25 13 4.2.1
PRE-ACTION VALVE ENCLOSURES EQUIPPED WITH LOW TEMPERATURE ALARMS
SHALL BE INSPECTED? correct answers WEEKLY. NFPA 25 13.4.3.1.1.1
ALARM VALVES AND SYSTEM RISER CHECK VALVES SHALL BE EXTERNALLY
INSPECTED "BLANK" correct answers MONTHLY. NFPA 25 13.4.1.1
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller FullyFocus. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for £10.21. You're not tied to anything after your purchase.